Home Blog Page 29

Whole House Ventilation

In this article we’ll show you four basic methods of whole house ventilation, which in theory explains concepts used in commercial applications. We’ll identify the advantages and disadvantages of each method of ventilation.

If you prefer to watch the video fo this presentation, you can scroll to the bottom.

Exhaust Ventilation Systems

Using exhaust as the primary method of ventilation requires that an exhaust fan creates a negative pressure within the space. The exhaust fan will pull air from the space and exhaust it outdoors. A path for outdoor air to get into the building must be created. The makeup ventilation air can come from leaks in the building construction, such as doors and windows, or from the installation of passive vents.

Whole House Exhaust Ventilation System
Whole House Exhaust Ventilation System

When the exhaust fan is running, it creates a negative pressure causing air to be drawn into the home through the cracks and vents. 

Exhaust systems are simple to install and are relatively less expensive than the other methods. The fan can be installed in the attic if available or on the roof. A single location for the intake of exhaust air can be provided or from multiple locations for a much better design. Air can be exhausted from spaces that generate pollutants, such as the bathrooms or laundry rooms.

The use of passive vents for makeup air prevents the reliance on leakage into the building from the building construction. Passive vents may require larger pressure differences than that produced by the exhaust fan to work correctly. 

With the use of negative pressure as the main method of ventilation, there is the concern that pollutants could be drawn into the space. Pollutants such as dust from attics, radon and mold from crawlspaces, fumes from attached garages, and flue gases from a fireplace or fossil-fuel-fired water heater and furnace. In addition to pollutants, in humid climates, moisture could be drawn into the space, so this method would not be recommended for humid climates. In cold climates the need to mix the outside air with indoor air may be required to avoid cold drafts.

Supply Fan Ventilation Systems

In stead of pulling air out of the building, a supply fan pressurizes the spaces by forcing outside air into the building. This causes the spaces to be under positive pressure, which forces air to leak out of the building through cracks, bathroom exhaust or kitchen range hood exhaust ducts, or through vents if provided. These systems are also one of the easiest and least expensive to install. Again the supply duct can supply one area or preferably several of the most occupied spaces.

Whole-house Supply Ventilation System
Whole-house Supply Ventilation System

By pressurizing the building using a supply fan, unwanted pollutants are minimized from entering due to the pressure relationship between indoors and outdoors. A supply system can also have the outdoor air first enter through a filter to remove dust and pollen.

Supply fan ventilation systems works best in hot or mixed climate regions. In colder climates these systems can cause moisture problems because they pressurize the space. In the cold winter, the warm inside air can be forced into exterior wall and ceiling cavities. If this air is humid, then condensation could condense out causing mold and mildew.

Since there is no conditioning of the air or the removal of moisture through an air conditioning coil before entering the space, these systems could use more energy compared with an energy recovery ventilation system. 

Balanced Ventilation System

The exhaust system creates a negative pressure, while the supply system creates a positive pressure. With a balanced ventilation System, the two cancel each other out to maintained balanced indoor air pressure. If supply air into the space equals the exhaust air volume leaving the space, theoretically you have a balanced system.

Whole-house Balance Ventilation System
Whole-house Balance Ventilation System

With a balanced system you’ll have a supply and exhaust fan serving the space. The strategy is the same when it comes to where the intakes and exhaust locations should be. Supply air should be located in the most occupied spaces, while exhaust should be in areas that generate pollutants.

Having multiple fans and ductwork makes this system more expensive to install and operate than a single fan system. These first three systems do nothing to temper the incoming air or to remove moisture before entering the spaces.

Energy Recovery Ventilation Systems

This whole house ventilation system will cost the most to furnish and install. It also will require more engineering to meet the needs of the spaces. Some energy cost savings comes with the use of a heat-recovery ventilator (HRV) or Energy Recovery Ventilator (ERV). They can reduce the operating cost by transfering heat or energy between the incoming and outgoing air streams. 

Energy or Heat Recovery Ventilation System
Energy or Heat Recovery Ventilation System

In the cold season, heat is transferred from the exhaust air into the cooler ventilation air entering the space. In summer, heat is transferred from the warm ventilation supply air entering the building to the exhaust air leaving. This helps reduce the load on the air conditioner due to the ventilation. 

See our other video on “Heat Recovery Ventilators” for more information.

Whole house ventilation options

Fire Dampers and Smoke Dampers

In this article we’ll show you how fire dampers and smoke damper work and why they are used. We’ll start with a single large air conditioner on the roof of a two-story building, but this could apply to larger buildings also.

If you prefer to watch the video version of this presentation, you can scroll to the bottom.

A main supply air duct feeds all of the first-floor spaces and is returned using an attic return from the spaces into the main return air riser. Each of the spaces will receive a connecting supply air duct and a return air grill that lets the air find its way back to the air conditioner through the return main.

Fire Dampers and Smoke Dampers, including combination Fire/Smoke Dampers
Fire Dampers and Smoke Dampers, including combination Fire/Smoke Dampers

The fan in the air conditioner creates a positive pressure on the supply side pushing the air through the duct, while the return side creates a negative pressure and pulls the air back to the AC unit. You will often find fire rated walls running the length of the corridors which is the life safety pathway for occupants existing the building during a fire. In this case we show a slab-to-slab protective fire barrier with a non-rated ceiling. The fire rated wall is to prevent fire from entering the corridor, so making holes in the wall would defeat the purpose.

To air condition the corridor we’ll install a supply air duct that penetrates the fire rated wall, and we’ll also provide a return grill in the ceiling with an opening in the fire rated wall to allow the return air to make its way back to the air conditioner. Of course, the supply and return won’t be next to each other as shown here, but this is for simplicity of the example.

If we don’t protect the openings, we made in the walls for our air conditioning ducts then smoke and fire could enter the emergency exit corridor, compromising the safe exit of the occupants. Since the return air is under negative pressure, the smoke could be sucked back into the air conditioner and sent back down the supply duct to all the spaces. This would be compromising the safety of all the occupants. 

Fire Dampers

Since we have penetrated the fire rated wall, we’ll need to maintain the fire rating by installing a rated fire damper at the supply and return air wall penetrations. Here is the definition of a Fire Damper according to the NFPA (National Fire Protection Association).

“A fire damper is designed to, and required to, close automatically upon detection of heat (such as a fusible link or heat detector) and to interrupt airflow and to restrict the passage of flame.” 

Fire damper
Fire Damper

Static and Dynamic Style Fire Dampers

Fire dampers are classified for use in a Static System, (a static system is an HVAC system designed to stop the movement of air within the system at the indication of a fire).  Then there is a Dynamic Systems (A dynamic systems is an HVAC system designed to maintain the movement of air within the system at the indication of a fire). So, in a static system the fan should be off, while in a dynamic system the fan will be running as part of an engineered smoke control system.

A fire damper works to protect the opening when the fusible link that holds the damper in the open position, melts. As the fire and heat builds up on one side of the wall, the fusible link reaches the melting point and releases the damper to fall and close off the opening in the duct or wall, preventing the fire from spreading to the other side.

Remember with a static style fire damper the HVAC system fan will be off, while with a dynamic style fire damper the fan will be running because it’s part of an engineered system to control pressure relationships between areas to move smoke out of the building or a protected zone. Dynamic fire dampers are designed to handle the pressure related to a fan operating. 

Smoke Dampers

Smoke is an important aspect of any fire, as most people that died in the MGM Grand fire in Las Vegas, died related to smoke inhalation.

Smoke Damper or Combination Fire/Smoke Damper
Smoke Damper or Combination Fire/Smoke Damper

The primary function of Smoke dampers according to the NFPA is to control the movement of smoke in dynamic air distribution systems, and they reduce the possibility of smoke transfer within ductwork or through wall openings. Smoke dampers are installed in corridor and shaft walls, and other barriers engineered to prevent the spread of smoke.

The smoke damper is designed to operate automatically to stop the spread of smoke throughout the air ducts. This is done with the use of smoke detectors that can be located within the duct or with the use of area detectors in smoke compartments.

Combination Fire/Smoke Dampers

There are also fire/smoke damper combinations that protect the opening using both techniques. According to the NFPA, a combination fire/smoke damper is used when a barrier is both rated for fire resistance as well as designed to restrict the transfer of smoke and will meet both the fire damper and smoke damper requirements.

Construction Trades Involved

The construction trades involved in the installation and maintenance of smoke/fire dampers and their scope of work include:

Mechanical Engineers

Mechanical engineers design the HVAC systems and smoke/fire damper layouts. They specify the types of dampers required and their locations to comply with fire safety codes and standards.

HVAC Contractors

HVAC contractors are responsible for installing the ductwork and integrating smoke/fire dampers into the duct systems. Their scope includes the physical installation of the dampers, the wiring required for damper operation, and commissioning of the system.

Electrical Contractors

Electrical contractors are involved in the electrical wiring required for smoke/fire damper activation. This may include wiring for fire alarm panels, smoke detectors, and damper actuators.

Fire Alarm and Life Safety Contractors

These specialists install and maintain fire alarm systems, including the components that detect smoke or fire and the control panels that trigger damper activation.

General Contractors and Subcontractors

General contractors oversee the coordination of all trades involved in the construction project. They ensure that the work of HVAC, electrical, and fire safety contractors is properly integrated into the building’s overall construction.

Building Inspectors

Building inspectors review and approve the installation of smoke/fire dampers to ensure compliance with local building codes and safety standards.

The installation and maintenance of smoke/fire dampers are crucial for the safety of occupants in commercial buildings, especially in the event of a fire. It’s essential that these systems are designed and installed correctly and undergo regular maintenance and testing to ensure they function as intended.

Fire Dampers and Smoke Dampers Explained

Duct Mounted Smoke Detector

Understanding Duct Mounted Smoke Detector Requirements in Commercial Construction

Protecting occupants from fire and smoke hazards is a top priority in building construction, and one crucial aspect of this is the proper installation of duct mounted smoke detectors. In this article, we’ll delve into the requirements for duct-mounted smoke detectors in commercial buildings, offering insights and guidance to ensure compliance with safety regulations, and show how they might be wired to a fire alarm panel.

If you prefer to watch the video of this presentation, then scroll to the borrow or click this link Duct Mounted Smoke Detector

How Duct Smoke Detectors Work

Air is drawn into the detector by a set of tubes extending into the ductwork. The long tube has holes along its length that are open to the direct air stream. The air enters the holes on the tube and is drawn into the detectors sensing chamber, surrounding the sensor.

Duct mounted smoke detector example of usage
Duct Mounted Smoke Detector

After entering the sensor, the air is exhausted back into the duct through a shorter exhaust tube. There are various technologies for sensing smoke, but the results are to prevent the spread of fire or smoke by the ventilation system. If a significant amount of smoke is detected a signal is sent to shut down an air handler, fan coil or air conditioner.

NFPA 90A Compliance

The National Fire Protection Association (NFPA) Standard 90A outlines the requirements for air conditioning and ventilation systems, including the installation of duct-mounted smoke detectors. It’s essential to adhere to these guidelines to ensure proper placement and functionality. This is required on air handlers and fan coils having a capacity of 2,000 CFM or 944 L/sec.

Duct Mounted Smoke Detector requirements
Duct Mounted Smoke Detector for 2,000 CFM (944 L/sec) per NFPA-90a

Placement and Spacing

Duct-mounted smoke detectors should be strategically located in accordance with NFPA 90A. Duct mounted smoke detectors are usually required to be installed downstream of the air filters and before any supply air branch ducts. This ensures that the smoke detector senses smoke before it enters any of the spaces connected to the supply. 

Return system smoke detectors are not required when the entire space served by the air distribution system is protected by a system of area smoke detectors.

Duct mounted smoke detectors are not a substitute for providing area smoke detection and early warning detection, nor is it a replacement for a building’s regular fire detection system.

Why use Duct-Mounted Smoke Detectors?

The primary function of these smoke detectors is to initiate the shutdown of the air handler fan within the specific unit it serves in case of the presence of smoke originating from components such as the motor, filter, belts, and similar elements within that unit. If the motor overheats it could cause a fire within the unit and blow smoke into the spaces before the return air senses the smoke. This is why the smoke detector is located downstream of the filter.

Testing and Maintenance

Regular testing and maintenance of duct-mounted smoke detectors are critical. Ensure that they undergo functional testing as recommended by the manufacturer and adhere to scheduled inspection routines to maintain their reliability.

In summary smoke detectors provide early warning of a problem within the ventilation system and are not used for area detection. Remember to check your local code for the conditions surrounding the proper use and placement of smoke detectors, as each code varies.

Learn How Duct Mounted Smoke Detectors work and where they’re located

Refrigeration Technicians Best Tools

Essential Tools for Every Refrigeration Technician: A Comprehensive Review

Are you intrigued by the inner workings of refrigeration systems and the vital role they play in our everyday lives? Whether you’re an aspiring refrigeration technician or a seasoned pro, understanding the tools of the trade is essential.

In this comprehensive review, we delve into the top tools that every refrigeration mechanic should have in their arsenal. These tools are not mere conveniences; they are the very instruments that empower technicians to diagnose, repair, and maintain refrigeration systems efficiently and effectively.

1. Manifold Gauge Set: Refrigeration mechanics rely on manifold gauge sets to simultaneously measure high and low side pressures in refrigeration systems. These sets are like the eyes of the technician, providing critical insights into the system’s condition. By providing real-time data, refrigerant gauges are essential for diagnosing issues and ensuring optimal system performance.

List of Gauge Manifolds

1- Shikha 5 Foot (see image)

2- Fieldpiece SM380V

3- Testo 550’s

4- Lichamp Gauge Set

5- Yellow Jacket 42004

2. Vacuum Pump: A vacuum pump may seem unassuming, but its role is monumental. It evacuates air and moisture from refrigeration systems before the introduction of refrigerant, ensuring that the system operates efficiently without unwanted contaminants.

3. Leak Detection Tools: Finding elusive refrigerant leaks is a challenge without the right tools. Leak detection tools, including electronic detectors and bubble solutions, play a crucial role in environmental protection and system efficiency by pinpointing these leaks.

4. Digital Multimeter: An HVACR technician’s electrical diagnostic prowess relies heavily on a digital multimeter. This tool measures voltage, current, and resistance in electrical components, making it indispensable for troubleshooting electrical issues.

List of Digital Multimeters

1- KAIWEETS Digital Multimeter (see image)

2- AstroAI TRMS 6000

3- AstroAI 4000

4- Astro 2000

5- Klein MM325

5. Pipe Cutters and Flaring Tools: Copper pipes are the lifeblood of many refrigeration systems, and pipe cutters and flaring tools ensure these essential components are accurately cut and shaped for the job.

6. Pipe Benders: The importance of smooth, kink-free bends in copper pipes cannot be overstated. Pipe benders are the secret to achieving these precise bends without compromising the integrity of the pipe.

7. Thermometers and Thermocouples: When it comes to temperature measurement, accuracy is key. Thermometers and thermocouples help technicians monitor temperatures at various points in the system, assisting in both diagnostics and cooling optimization.

8. Tubing Tools: Properly preparing tubing for installation is a fundamental step in any refrigeration project. Tubing tools, such as deburrers and reamers, ensure that tubing is ready for action.

9. Hex Key Set: Hexagonal screws and bolts are commonplace in refrigeration systems. A set of hex keys is a technician’s trusty companion for swiftly disassembling and reassembling components.

10. Oil Pump and Oil Injector: Lubricating oil is the lifeblood of compressors. Oil pumps and injectors ensure that the compressor functions optimally by delivering the right amount of lubrication.

11. Torque Wrench: Precision matters in refrigeration systems. Torque wrenches guarantee that bolts and nuts are tightened to precise specifications, safeguarding components and maintaining proper seals.

12. Digital Scale: In the intricate world of refrigeration, precision is paramount. This is where a digital scale steps in as a silent but indispensable partner for refrigeration mechanics. Why? Because refrigerants, lubricants, and various chemicals must be added to systems with meticulous accuracy.

A digital scale ensures that the right quantities are added, helping maintain the system’s efficiency, performance, and, perhaps most importantly, the environment. It’s not just about getting the job done; it’s about getting it done right, and that’s where the digital scale shines. So, let’s weigh in on the importance of this often-overlooked tool in the refrigeration technician’s toolkit.

List of Digital Scales

1- Eiltech LMC-200A (see image)

2- Xetron High Accuracy

3- Eiltech LMC-300A

4- Yellow Jacket 68862

5- VIVOHOME Precision Electronic

These tools are the cornerstone of any refrigeration technician’s toolkit. Stay tuned as we dive deeper into each of these essential instruments, unveiling the art and science behind their usage, and why they’re indispensable for refrigeration technicians around the globe.