Sheet Metal Seams

Chapter #6 – Sheet Metal Seams

Seams run longitudinal along the length of the duct run, while joints run transverse (across). Seams run parallel to the air flow, while joints are perpendicular to the air flow. The seams hold together the duct or section of a single fitting as opposed to a joint that connects two separate pieces together. The seam is highlighted in the below image.

Each section of duct can have 1 to 4 seams depending on how large the duct is. Really large ducts and fittings can have more than 4 seams as required to provide strength and span wide areas, but in most cases there will be 1 or 2 seams.

Seams
Seams

Snap Lock  and the Pittsburgh seam are the most typical seams used or specified in the HVAC commercial construction industry that we have witnessed. We show them here with a few others.

Seams
Three types of Seams

Standing Seams

When ducts get too wide they could require an additional seam to add strength and span the greater distances. The use of a standing seam provides strengthening for the larger ducts. Depending on the size of the duct, the standing seam will extend upward either by 1 inch or 1-1/2 inches.

Standing Seam
Standing Seam

Pittsburgh Seams

Pittsburgh Seam
Pittsburgh Seam

The Pittsburgh seam is used for pressure classes and duct sizes larger than the Snap Lock seam can handle. The Pittsburgh seam comes in small and large sizes depending on the pressure requirements of the ductwork.

Pittsburgh seam
Assembly of a Pittsburgh Seams

To lock the two ends of the Pittsburgh seam together it is run through a Pittsburgh Lock machine that folds over the standing lip, effectively locking the two pieces together. If the fabrication shop doesn’t have an automatic Pittsburgh seam machine then there are hand held models or it can be hammered over by a shop worker the old fashion way.

Assembling a pittsburgh seam
Assembling a Pittsburgh Seam
Closing a Pittsburgh seam
Closing a Pittsburgh Seam

Pittsburgh Seam on Ductwork

Here is a video of a hand held Pittsburgh seam closer.

Pittsburgh Seam Closer

Pittsburgh Seam on a Fitting

This next video shows a sheet metal fabrication shop worker using Pittsburg seams on an elbow.

Button Punch Snap Lock

A Snap-lock roll forming machine will be one of the shop fabrication machines that gets highly used, as this makes the seam for the smaller, low pressure ductwork and fittings. Each piece gets one of its ends rolled to form basically a male and female longitudinal seam connection that gets knocked together and locked in place. The pieces are then bent to form an “L” shape in the case of a two piece fitting. Larger pieces may require four pieces to make the fitting.

Seam Question
Snap Lock Seam

These machine vary on their production. Somewhere around 60 feet per minute for the seam.

Watch the video below to see how quickly this seam is made and assembled.

Welded Seams

For duct systems requiring a heavier duty seam as can be found in some lab exhaust systems, the seam can be fully welded longitudinally. A piece of sheet metal will be cut to the proper width based on the circumference of the round size required and then put through a roller to shape the metal into a circular pattern. The longitudinal seams will be held together as the seam is welded. The ends can have a flange welded on so section of straight round duct can be fasten together or to a fitting with a flange.

Fully Welded Round Fittings
Fully Welded Round Fittings

Grooved Seams

grooved seam
Slip Roll Machine
Slip Roll Machine

As shown below the metal is slipped into the roller and then it’s rotated around the three rollers. To make a greater or small circumference you adjust the position of the back roller.

Slip Roll Machine Example
Slip Roll Machine Example

Now let’s look at chapter #7 to see how to make a sheet metal Joints.

Sheet Metal Plasma Cutter

Chapter #4 – Sheet Metal Plasma Cutter

A plasma cutter is a large table where a piece of sheet metal is cut to make a fitting according to patterns setup in the shops fabrication software. The software optimizes the patterns to minimize wasting the material, any excess material scrap is placed into a recycle bin. A computer on the machine tells it how to cut each piece. This will help reduce your waste factor for those estimators that work with their shop foreman to figure how much waste to account for with the various pieces of equipment.

Plasma Cutter
Plasma Cutter

Some plasma cutters can cut up to 1-1/4” thick metal depending on the manufacture and model number of the cutter, but in the Heating Ventilating and Air Conditioning industry we won’t need that ability as most of what we need fabricated will fall between 26ga and 16ga.

The Plasma cutter is used to make fittings as straight duct will be made off a coil line which will discuss shortly. The size of the Plasma cutter table varies based on the shops requirement and the manufactures available models, sizes such as 5’ x 10’, 6’ x 10’, 5’ x 20’ and 6’ x 20’.

The Plasma cutter has an exhaust fan to remove the gas from the cutter. After the cutter has completed cutting the shapes, the sheet metal shop worker separates the shapes and puts the scraps in a bin for recycling. Each piece will have a sticker that gets slapped on it or marked by the shop worker that indicates many aspects of its assembly requirements and the project it’s being fabricated for.

Plasma Cutter Table

If a fabricated section has a sticker as shown below it will be applied to the cut piece. It will show a pictogram (#1) of the piece with its gage and dimensions (#2) and the joint and seam (#3) requirements, in addition to the job name and static pressure or specifications used (#4). Another important designation on the sticker is where the fitting is located (#5) in the building and what system it serves (Supply Air, 2nd Floor, West, VAV-13) This information will save on material handling, as it is clear from the label exactly where this fitting is to be installed within the building.

If you watched the video above you would have seen one of the fabrication shop personnel placing stickers on each piece.

Plasma Cutter Stickers
Plasma Cutter Stickers

Now that shapes have been cut by the plasma cutter the next step will be to make the seams and joints so that the pieces can be attached together to make a fitting or a short piece of ductwork.

The pieces cut from the plasma cutter might get put through the beader for strengthening, and then through the seamer to make a Snaplock or Pittsburgh Seam and through a roll former to make a TDC or other type of joint depending on the requirements of the fitting or short duct section. If the fitting or duct joint requires internal lining, then this will occur before assembling.

One of the last stops in the shop will be to assemble all the pieces together into a finished fitting or short section of ductwork. If required, tie-rods will be inserted to provide support for larger fittings and duct sections. Also, external reinforcement will be added after assembly if required.

Duct Sealer will be applied to all internal seams and penetrations.

The pieces should flow efficiently through the fabrication shop to optimize time, avoiding unnecessary steps for the shop workers. 

Watch this short video and look for the notches cut into the metal at the point where it will be bent. Notice also the shape of the last part cut, as it appears to be the cheek of an elbow, and the first piece will be the throat of that elbow.

Plasma Cutter Table

Coil Line Feeding a Plasma Cutting Table

For those shop that can afford the capital to purchase a coil line dedicated to a plasma cutting table as shown in this video below, will have the ability to safe on the labor required to pull flat sheet metal stock on to the table.

Notice that the shop personnel have attached identifying stickers on each piece of sheet metal being cut. This will help in the assembly process and when material handling at the job site in order to get the right fitting in the correct location on the project. This is really helpful the larger the project is, as hunting for the correct fitting when you’re working on a large building is a big waste of time.

Coil Feeding Plasma Cutter Table

Now let’s look at chapter #5 to see how using a Spiral Machine can save on material waste and labor.

Sheet Metal Coil Line

Chapter #3 – Sheet Metal Coil Line

Those fabrication shops that have invested in a coil line will find it less labor intensive to fabricate straight pieces of ductwork.

Sheet metal coil lines are available with many optional pieces of equipment that can be added on to perform an additional function on the path to creating a fully sectional piece of ductwork.

The full capabilities of the coil line begins where several rolls of differing gauges of metal are housed in large heavy rolls and end where the sheet metal is bent. Between the beginning and end are various pieces of fabrication equipment that perform special functions in the process of making a piece of duct for the HVAC industry.

Standard coil widths include 48” and 60”, which can make anywhere from a 4 foot to a 5 foot long piece of duct. Also, as an option are coil widths of 72” for a duct length of 6 feet, minus flange allocation. Gauges will range from 16ga to 30ga.

Remember when watching some of the shop fabrication videos below that fabrication shops are very noisy at times when the equipment and workers are in full operation, as they are working with sheet metal.

This first video will animate the total process. We recommend that once you finish this chapter that you watch this video again to identify all the steps you are going to learn about in this chapter.

Automated Duct Making Coil Line

Sheet Metal Coil Line

The below image shows that a forklift is being used to load the sheet metal coil onto a coil machine. These coils are very heavy and require machinery or an overhead crane system to load them onto the coil line equipment.

Sheet Metal Coil Setting
Sheet Metal Coil Setting

The coil line process steps are outlined below and are covered in greater detail later in this course.

  1. SHEET METAL COILS – Choose which coil width and gauge of sheet metal is required for the project.
  2. STRAIGHTENER/LEVELER – The process of straightening the sheet metal.
  3. BEADER – This stiffens the metal by putting a bead down the sheet metal
  4. NOTCHER – The notcher will cut out (notch) small portion of the duct at its edge where it will be bent
  5. SHEAR – This is when the sheet metal gets cut at the perfect point.
  6. SEAMERS – This machine installs the Snaplock or Pittsburgh seam along its length at the point where it will attach to the other side. One seam will be a female seam and the other male for a perfect fit.
  7. JOINT (Rollformer) – The metal has its end roll formed to create the ends of the duct that will join up to another piece of duct or a fitting.
  8. LINER – If required liner will be added.
  9. BREAK – This is the final step in the automated coil line. This last piece of the coil line will bend the sheet metal into either an L-Section (2-sided), U-Section (3-sided) or Full-Wrap (4-sided)

Watch the video below and see if you can identify the various coil line steps in the process of forming a section of duct.

We begin with the coil of a particular width and gauge, which gets fed into the straightener. The purpose of the straightener/leveler is to remove the metals tendency to want to remain curled up as it was within the coil from the manufacture. After this it goes through the beader, which puts several beads across the sheet metal to stiffen it in its finished form.

Then the metal gets notched at the points where the metal will be bend so as to allow for and easy bend along its longitudinal length. The next section will shear the duct, cutting it at the perfect point along its length. The seaming section is next where it will have a female seam on one side and a male seam installed on the other by their respective seamers, such as a Snaplock or Pittsburgh seam.

Then the metal goes through the roll former, which creates the joint end of the sheet metal duct, such as TDC, Drive Slip or completely raw for the attachment of a proprietary joint such as Ductmate. Next liner will be added if the specifications call for the duct to have internal liner. The automatic duct liner feeds from a coil of liner material while applying a liner adhesive to the sheet metal and then automatically pins the liner to the sheet metal.

And finally the metal is bent using the break to create an L-Section (2-sided), U-Section (3-sided) or Full wrap (4-sided) section. The brake is a heavy duty hydraulic sheet metal bending machine that will fold your duct in preparation for assembling.

Sheet Metal Coil line
Sheet Metal Coil line

Step # 1 – Sheet Metal Coil Line

Galvanized steel is defined as a carbon steel sheet coated with zinc on both sides. Hot Dipped Galvanized for the HVAC industry is usually specified to be coated either as G-90 or G60. The coating indicates the amount of zinc applied to each side of the carbon steel. The most common gages used are from 16 ga through 26 ga. The use of the lighter gages are not as common in commercial construction as it is in residential construction.

Sheet Metal Coils
Galvanized Sheet Metal Coils

The most common width of the coils used in the HVAC industry is 36”, 48”, 60” and 72”, with the 60” width coil being the preferred width. The Wider the coil, the less joints you will need, as a 60” wide coil can make a 5 foot section of duct using Ductmate connectors, as opposed to only a 3’ foot section with a 36” coil width.

For example if you had 90 feet of straight duct, it would require;

  1. 30 pieces of 36” (3 foot) sections of duct 3’ x 30 = 90’
  2. 18 pieces of 60” (5 foot) sections of duct 5’ x 18 = 90’

It’s better to handle fewer pieces, in addition, the more pieces you have, the more it cost for gaskets, corner pieces and clips because you have 12 additional joints to make.

The coils are loaded onto the automated coil line using a forklift or overhead crane.

Step # 3 – Beading

The ductwork is Beaded or Cross Broken (#4) to provide strength across its surface area. Duct beading is the preferred method. The duct is run through a bead machine that puts a ridge or dimple across it transverse width every 12” or so. This will help reduce sagging of the metal.

Beaded Duct
Beaded Duct

The purpose of cross-breaking or beading ductwork is to provide support for large spans of ductwork. For ducts that are 19” and greater in width and 10 Ft2 of unbraced panel area will require cross-breaking or beading. This requirement is for duct classifications of 3” static pressure and down and 20 gauge or less thickness. Ducts built to 4” static pressure or greater don’t require cross-breaking or beading as the increased thickness and reinforcement requirements provide the added support benefit. Beading is spaced every 12” apart, running parallel with the joint of duct, but direction of bead can be random on fittings.

Ductwork Cross breaking
Ductwork Cross Breaking

Step # 4 – Notcher

The machine will notch the duct at the points where they need to be folded. The below image shows a four sided piece of sheet metal ductwork notched (#1) at the points that it will be bent by the Brake. The yellow highlight shows the line of folding (#2) that will happen with the brake in order to make the four sided piece of duct. Notching is how sheet metal is allowed to go through the roll forming machine where the joint is made.

The notching allows the roll-formed edge (#4), such as a TDC/TDF or S & Drive the ability to avoid the interference from bending at the corners. There is no way to bend the metal after its been through the joint (#4) making process without having the corners notched (#1). Ductmate doesn’t require notching as it isn’t put through the roll former, as it is an added flange that gets put on after the duct is assembled.

Notching
Notching

The depth of the notch is determined by which joint type will be applied to the end, such as TDC or S and Drive. TDC requires a deeper notch then S&D (S & Drive). There are different types of notching but they all have the same goal in mind.

Step # 5 – Sheet Metal Shear

Another piece of shop fabrication equipment is the shear, which comes in various forms, from automatic to manual. The fully completed coil line uses an automatic shear. The shear cuts the sheet metal at the point needed to give the proper width of duct.

There are also hand held electric shears. Shown below is a manual stand-alone foot operated shear. Once the metal is position in the machine you push down with your foot on the long bar that near knee height.

sheet metal coil line Q10
Foot Operated Shear

Below are two videos, the first one is a short demonstration of a foot shear, the second is a longer video of the many steps in making a piece of sheet metal and the various tools used in marking and measuring.

Foot Powered Shearing

This next video is a little over 8 minutes, but gives a good overview of the process of cutting a piece of sheet metal with a foot operated shear.

Sheet Metal Shearing

Step #6 – Sheet Metal Seams

Seams are created along the longitudinal length of the duct or fitting to fasten one section to another, as opposed to joints that connect one length of duct section to another, or a joint of duct to a fitting. Seams seal to make one section of duct or a fitting.

The longitudinal seam will be either Snap Lock or Pittsburgh Lock and is formed on a machine that will roll form the flat edges into one with a female and the other with a male end.

Snap Lock Seam
Snap Lock Seam

Pittsburgh seams are used on increased pressures, above those acceptable for Snap Lock.

Pittsburgh Seam
Pittsburgh Seam

The video below is a little grainy, but you can see that the rollers will bend the flat edge of the sheet metal, each successive roller bending the metal a little more until it reaches the shape required by the last roller. These machine is a stand-alone piece of equipment which in a complete coil line would be part of the automated process.

Pittsburgh Seamer

Step #7 – Roll Forming Machines

Depending on the seam type, the flat metal cut by the Coil Line or Plasma cutter will get  put through the roll former to form a Snap Lock Seam or a Pittsburgh Seam. These are the two most common seams, so they are the ones we will be using through-out this training program. The seam takes two pieces of metal and locks them securely together. The seam runs longitudinal and the joint runs transverse.

Step #8 – Liner

Duct is often provided with internal liner for mostly acoustical reason and for its thermal properties for air ducts installed outdoors where wrapping duct is not practical because of the cost. The video below is of a portable pinspotter machine that is not part of the automated coil line, but will show you how liner pins are fasten to the duct to hold the liner in place.

Portable Pinspotter for Attaching Liner to Duct

In an automated coil line with a liner station, the metal will be sprayed with adhesive before the liner is applied, followed by the pins. In non-automated systems there will be a table area where the metal will be sprayed with adhesive before the liner is attached to the interior of the duct or fitting.

In the below video you will see several methods used in the coil line process for attaching liner to the duct, in addition you will see another manual method of attaching the pins that hold the liner in place.

Linacoustic

Step #9 – Duct Break

Before the sections of duct can be assembled they need to be bent to form an “L-Shape”, “U-shape” or 4-sided single piece which comprises the duct. The break is a machine that is used to bend sheet metal. The metal is inserted to a point where the bend is required and then the machine automatically activates the break to bend the metal.

Sheet Metal Brake
Hand Brake

Some shops still use a manual hand break (shown above) where the operator pulls a lever which causes the machine to bend the metal. With this portion complete you now have two “L” sections, or a “U-Shaped” section that will match up along a male and female companion seam. For smaller ducts it might be possible to make the duct section out of a single piece. The seam gets knocked together either as a snap lock or Pittsburgh seam as described previously.

Watch this video to see how metal is bent using a brake. These types of brakes go by various names such as Box Brake, Finger Brake or Pan Brake. Notice how the shop worker inserts the notched section of the flat metal into the machines notch guide to position it correctly for where the fold will occur.

Duct Brake

Duct Reinforcement

Reinforcement provides for the strengthening of the ductwork under certain conditions as dictated by the construction standards. The construction standards are driven by many factors including the pressure class, the size of the duct or fitting, the length of the duct and the local code adopted construction standards table.

Reinforcement can be accomplished by adding angles, channels, and Condu-locks with EMT. There are various other methods depending on the construction standards that provide jurisdiction over the project location. The standard could be an adoption of the SMACNA standards or the jurisdictions own version of something similar.

Coil Line Feeding a Plasma Cutter

Instead of having the coil line feed a sheet metal duct making process, it can feed lengths of coil duct onto a plasma cutter. This avoids having to purchase flat sheet stock and material handle each piece onto the plasma cutter. Watch the video below to see how a coil line machine can feed a plasma cutter to save time and money.

De-coiler

A Simplified Coil Line

In the below video you can hear the loud notching of the metal as the machine punches (notches) out at the point where the duct will be bent and or cut. The coil line machine cuts the section while creating a longitudinal seam, the point at where the duct sections will attach. The machine provides all aspect of the duct section, including straightening, beading, notching, joint formation, cutting, seams and bending.

The only thing the machine doesn’t do is the final banging together the single or two piece sections of duct along the seam. It also doesn’t install the corners pieces where the sections are bolted together.

Duct Assembling

Ductwork can be made into one, two or four pieces. One piece duct or full wrap duct is fabricated with one continuous piece of sheet metal and is limited in size by the fabrication equipment. As the duct gets larger and larger, more pieces will be required to make the duct. Two pieces (aka “L” sections, half sections, knocked down) are easier to ship, but more costly for the field labor, as they have to assemble the sections before installing.

Check what an “L” Section looks like coming off an automated break.

L-Section Duct

The Pittsburgh seams are knocked together with a Tinner’s Hammer or an automated tool that accomplishes the same thing, that is to bend over the seam to lock the sections together.

Tinners Hammer
Tinners Hammer

Coil Line (Fast Time Lapse Video)

This next video shows a shop worker knocking together sections of duct, installing the corner pieces and using an automatic Pittsburgh seamer to bend over the seam and lock the sections in place.

Now that you have an idea of what happens from the coil line to the end product, see if you can identify some of the following steps in this sped up video of a coil line. You’ll notice that when the sheet metal first appears in the video it has already been straighten, beaded and notched.

The next step you will see is the application of the male and female seams which is done under the white/beige colored metal boxes that protect the roll formers. Then it moves down to the roll formers that put the joints on each end, before finishing by being bent. Replay the video until you notice each of the steps being performed.

One more quick video from coil line to end product.

And one more that shows you a 4-sided, one piece wrap.

Making Square to Rounds

Making a square to round requires that you make small bends along the length of the square to round to form the shape. Fabrication shops use various pieces of equipment such as the break to make these small creases incrementally along its length to make the square to round. This can be done faster with this NAMCOR Striker machine. See the video below to get an understanding of how the machine makes a square to round.

Square to Round

Now let’s look at chapter #4 to see how using a Plasma Cutter can save on material waste and labor.

Introduction to Sheet Metal Fabrication

Chapter #1 – Introduction to Sheet Metal Shop Fabrication

The sheet metal fabrication shop is where all the ductwork and fittings are fabricated for the installation of air conditioning and heating systems, the systems that carry the air from the source of cooling or heating to the room to be warmed or cooled.

The larger sheet metal fabrication shops will mostly likely be running on software that automates various pieces of shop fabrication equipment, while some will also be fully integrated with the detailing and estimating departments.

Detailing

Detailing is the process of creating shop drawings or detailed drawings that are coordinated with the buildings structural elements and other trades to avoid interferences that may occur between these trades. The detailed drawings will show the distances that your sheet metal or other HVAC components will be hung from columns, floors and other reference points. The detailed drawings also show how the sheet metal is to be fabricated. (see chapter on Sheet Metal Shop Drawings)

In the image below there is a very large duct (10’-6” x 2’-0”) that has been detailed to be hung 6’- 6” from structural column #20, and 10’-6” from the floor to the bottom of the duct in order to miss the structural steel beam. A detailer coordinates what the mechanical contractor needs to install within the building while trying to avoid collisions with building components and other trades to make sure everything fits as designed. This helps avoid change-orders.

Detailing needs to occur before the sheet metal fabrication shop makes one piece of duct. This is done by the sheet metal detailer using some form of CAD (Computerized Aided Design) software to layout the sheet metal on the drawings indicating duct sizes, lengths and joint types.

Detailing Reference Lines
Detailing Reference Lines

The benefit of using one software database for the sheet metal fabrication shop equipment, like the plasma cutter table and coil line is consistency of standards with the detailing and estimating departments. If the shop isn’t automated, then everything will have to be done manually for every piece of sheet metal.

Sheet Metal Order Forms

The sheet metal shop will receive an order from the detailer on some type of written or automated form created for this purpose (see example below). This form could also be used to order from an outside sheet metal fabricator if you don’t have your own sheet metal fabrication shop.

The form will indicate all the required information for each piece ordered, such as the material required, duct or fitting size, pressure class, lining and size, and joint ends required. Much of the rest of the requirements will be dictated by construction standards, whether SMACNA or in-house standards or a combination of local and industry requirements. Don’t worry we are going to cover all of these topics in the following chapters.

Shop Order Form
Shop Order Form

On the partial shop order form above there are two items ordered, the first one is a straight short piece of duct (#3) and the second one is a 90-Degree Elbow (#4). The duct and elbow both show the joint to be S & D (Slip & Drive) and the size to be 20” x 18”. This form can have 6 to 9 squares available for defining the requirements for duct and fittings. This form can also be used to just get a quote from your sheet metal fabricator.

SMACNA Standards

The sheet metal fabrication has to be built to some standard in order to maintain consistency and comply with the local code where the sheet metal is to be installed. SMACNA (Sheet Metal and Air Conditioning Contractors National Association) is the most used standard in HVAC sheet metal fabrication shops. SMACNA provides for various methods of fabrication for ducts, joint and seam types, in addition to various material types based on the pressure class.

Using SMACNA standards the shop will build pressure class tables that correspond to the various pressure classes.

Pressure Classes

Pressure classes define material thickness and reinforcement requirements. The pressure class relates to how much pressure the sheet metal ductwork will be exposed to by the fan when its blowing (positive pressure) or sucking (negative pressure).

Just think of how a balloon is blown up; the pressure created by you blowing into the balloon puts pressure on the wall of the balloon stretching it out the more you blow. The blowing up of a balloon or your car tire is an example of positive pressure and your vacuum cleaner is considered negative pressure as it sucks in air.

Below is the chart for SMACNA 2” pressure class. As the size of the duct increases, so does the thickness of the material indicated by its gage. Remember that the lower the gage number the thicker the material, similar to the game of golf where the lower the score the better. We will cover all of this in more detail in other chapters.

SMACNA 2 construction standards
SMACNA 2 Construction Standards

Fabrication Shop Cost

The question often asked by those companies that have their own fabrication shop is whether the shop pays for itself. The cost of a sheet metal fabrication shop is capital intensive with all the required equipment, in addition to the labor cost to keep a shop operating during high and low periods. The question is it less expensive to purchase the sheet metal from another sheet metal fabricator or to make it yourself.

Keeping track of the utilities, indirect labor, insurance, trucks, tools, rent and equipment cost that it takes to operate a sheet metal fabrication shop is important to understanding whether it makes more sense to purchase or make your own sheet metal. The burden cost of having your own sheet metal shop needs to be considered and analyzed before investing in the costly operation of a fabrication shop.

The total cost of the sheet metal fabrication shop is important in order to understand the shop burden that needs to be recovered. The shop burden is the total cost to run and operate a sheet metal fabrication shop. This shop burden will be recovered at a rate equal to whatever metric is being used to recover the cost. If this metric is based on the quantity of hours worked in the shop, then a labor burden will be added to the hourly rate for each shop worker based on the total expected hours in a year.

Burden Based on Labor Cost

Burden Cost $500,000 / 25,000 shop hours = $20/hr burden rate

Burden Based on Pounds

If the burden rate is based on pounds fabricated in a year, than the following simplified calculation could be used;

Burden Cost $500,000 / 1,000,000 Lbs = $0.50/Lb Burden Rate

Sheet Metal Shop Labor Feedback

Do you know what type of productivity your shop is producing? Does your shop keep productivity numbers monthly so you can determine what is the shops average production rate in pounds per hour? It is very important for your shop to keep track of its productivity so you can bid the current job at realistic numbers.

How many pounds of metal does the shop fabricate in a year and what is the total cost to operate the shop. The shop needs a method to measure the billable rate to charge per hour for the various personnel in the shop.

The cost to run the shop from the previous year is used to derive at a value that is used for the current years job costing. In the example above, the shop would add $20.00 per hour on top of the labor cost to recover the cost burden of owning and operating the fabrication shop.

If the shop used material cost to add burden cost, then adding and additional 50 cents to each pound that the shop fabricates would recover the annual burden cost of owning and running the fabrication shop.

As is obvious from the two examples above of owning and operating a fabrication shop above, the critical factor is determining how many hours or pounds of metal that will be used in the current year as opposed to the previous year of which the data is forecasted from.

Summary

Remember that the process begins by a detailer using some form of software to detail the project to fit within the structure and avoid collisions with other trades. If the project is small then computerized detailing might not be feasible.

Next the detailer will fill out some type of order form which defines the duct or fitting size, material thickness, seams and joints in addition to other requirements we’ll cover later.

The detailer will take into consideration the pressure class, that is the amount of pressure the duct will be subjected to by the fan.

The sheet metal fabrication shop will then begin the fabrication process based on what the detailer has requested to be made.

Now let’s look at chapter #2 to see what the most common materials used for ductwork in commercial HVAC projects.

  • Chapter #1 – Introduction to Sheet Metal Shop Fabrication
  • Chapter #2 – Sheet Metal Materials
  • Chapter #3 – Sheet Metal Coil Line
  • Chapter #4 – Plasma Cutting Table
  • Chapter #5 – Spiral Machine
  • Chapter #6 – Sheet Metal Seams
  • Chapter #7 – Sheet Metal Joints
  • Chapter #8 – Sheet Metal Shop Fabrication Productivity
  • Chapter #9 – Casings and Plenums