Home Blog Page 63

Sheet Metal Duct Sealer and Leakage

Chapter #6 – Sheet Metal Duct Sealer and Leakage

Duct Leakage

Duct leakage is a factor of the static pressure in the ductwork that allows for leakage to occur through holes, seams, joints and penetrations. Leakage is a loss of energy, which means a loss of money. This is why it’s so important to seal the ducts and to prevent leakage. Leakage can also occur at equipment and accessories that are installed into the system including dampers, smoke/fire dampers, VAV Boxes and access doors.

SMACNA Duct Seal Classes

Ducts are required to be sealed according to SMACNA Table 5-1 based on the duct pressure class (#1), which is broken down into three categories of pressure. Depending on the pressure class of the duct, there will be a corresponding Seal Class (#2) from C to A.

As the pressure increases in the ductwork the applicable sealing requirements (#3) will apply to various aspects of the ductwork, starting with Transverse Joints Only (Seal Class “C”), then Transverse Joints & Longitudinal Seams (Seal Class “B”) and finally All Transverse Joints, Seams and Wall Penetrations (Seal Class “A”).

Recommended Leakage Class
Recommended Leakage Class

Duct Sealing

There are various sealing requirements.

This video shows how duct sealer is applied with a brush. It appears to be a messy job, but the idea is to make sure that all the joints and seams are air tight so as to avoid duct leakage, including brushing sealer over all screws used in fabrication. Ducts that leak are wasting energy and preventing the conditioned air of doing its job of providing a comfortable environment for the occupants.

Duct Sealing

There are various types of sealer including some that are required to be of low or no VOC (Volatile Organic Compounds) when a building is seeking to get LEED (Leadership in Energy and Environmental Design) certified or when requested by an environmentally conscious owner. The IEQ Credit 4.1: Low Emitting Materials is worth 1 point in the LEED certification program. This LEED credit applies to various sealants and adhesives used on the interior of construction projects in addition to duct sealer, items such as carpet and floor adhesives.

The Adhesives, Sealants and Sealant Primers must comply with South Coast Air Quality Management District (SCAQMD) Rule #1168.

Joint Sealing

Joints are sealed with Butyl Gasket to prevent leaks at the connection points between ducts, fittings and accessories.

Applying Gasketing

Duct Leakage

SMACNA doesn’t recommend pressure testing on duct pressure classes of 3” wg and less, as its not economically feasible. Be sure to check the specifications and your local or state energy code for this requirement. Leakage testing could be shown in the Testing & Balancing or the Ductwork section of the specifications.

Some states, like California require pressure testing on small systems (spaces 5,00 Ft2 or less) when 25% or more of the ducting is located in a non-conditioned space, one not intended to be occupied by people. This applies to both new and renovated projects.

Also some of the utility companies that offer energy saving incentives or rebates require pressure testing to confirm a maximum level of leakage in order to qualify for their program.

Sealing Ductwork
Duct Leakage Test

Duct Leakage Allowed

SMACNA publishes Table A-1 “Leakage as Percentage of Flow in System” that if specified in your local code or the design specifications, shows the percentage of leakage (#5) at various Static Pressures (#1) and Leakage Classes (#2). This is also effected by a calculation (#4) of the Fan CFM divided by the Ducts Surface Area (#3), shown as; CFM/Duct Surface Area. The product of the calculation is available at 2, 2.5, 3, 4 & 5 (#3).

Duct Leakage Percentage Table
Duct Leakage Percentage Table

Note that as the pressure increases (#6) so does the percentage of duct leakage. As an example, if you had a duct rated for 2” static pressure and the specifications called for a leakage class of 16, you would get a rate of 13% leakage, assuming your calculation (#3) for Fan CFM divided by Duct Surface Area equaled 2 or less.

Item (#7) above shows what the Table 5-1 “Recommended Leakage Classes” above would look like on this leakage rate chart. Item #7 shows for rectangular duct (highlighted in blue), while item #8 on the chart above is reflective of round duct (highlighted in green).

Sheet Metal Field Installation Course

Sheet Metal Duct Hangers

Chapter #3 – Sheet Metal Duct Hangers

Air conditioning ducts and pipes need to be supported according to code approved methods. You need to confirm that the hangers you intend to use are approved in the local area where the building is located. Mechanical engineers will specify the approved hanger methods in the specifications if provided.

Hanger requirements vary based on locale, but will often consist of two to three parts, the upper attachment (highlighted in blue) which attaches to the structure, the vertical hanger piece (highlighted in green) and the lower attachment (highlighted in red) which attaches to the duct.

There are many different upper and lower attachment types. A few are shown here for concrete.

Hanger Upper Attachments

The upper attachment portion of the hanger attaches to the building structure. The type of upper attachment to use is conditional upon the type of structural element it will be attach to. Common materials are wood, concrete and steel beams. The hanger’s upper attachment will then be connected to the vertical support piece which most commonly is a hanger strap, threaded rod or wire. Hanger strap are made from strips of galvanized metal ranging in gauges from 16ga to 26ga

Concrete Inserts

In commercial construction, concrete is often used to construct the floors, which can be constructed in place with forms or poured onto some form of metal decking.

The concrete insert will need to be installed before the concrete is poured when using metal decking. This will require that the hanger insert (the upper attachment) be placed on the floor above where the hanger is required. For example, if you are hanging duct or piping on the first floor, you would need to put the concrete insert into the floor of the second floor. Watch the video below to get a better understanding of what we mean.

Blue Banger Hanger

(See image below) You could use a simple bent flat bar (#1) that penetrates the floor deck (#3) and which gets covered in concrete to fix it in place. Field labor would spot the location for the hanger and punch a hole in the metal deck, then drop the sheet metal hanger through the punched hole, making the hanger available for the floor below.

With this type of hanger, the layout occurs on the floor above. This is best accomplished using some form of GPS laser layout tool, that automates the process based on CAD drawing hanger locations.

Hanger Strap
Galvanized Hanger Strap

 

Concrete Deck Installation Procedure

This upper attachment is inserted through a hole that is punched into a metal deck. The metal deck gets concrete poured onto it creating the solid floor. The metal deck remains in place as part of the floor assembly.

Blue Banger Concrete Insert
Blue Banger Concrete Insert
Concrete Inserts
Concrete Inserts Installation Procedure
Concrete Inserts Installation Procedure
Concrete Inserts Installation Procedure

Formed in-place Concrete Floor Inserts


This hanger upper attachment is hammered into the wood forms before the concrete is poured. After the concrete has hardened and the wood forms are removed leaving the upper attachment embedded within the finished concrete floor. The upper attachment allows a threaded rod (vertical hanger) to be screwed into its exposed female threaded bottom portion.

Powder-Actuated Concrete Shot Pins

When working in existing structures with concrete flooring, you might use a concrete shot pin if approved by the specifications and building ownership. This allows you to use a special powder actuated tool that shoots the upper attachment into the concrete. The tool uses a small shell filled with gun powder to force a pin into the concrete. The power-actuated shot pins should not be used in light weight concrete or concrete that is less than 4” thick.

Powdered Actuated Shots
Powdered Actuated Shots

Using a powder actuated shot that shoots your hanger into the concrete is a fast and convenient way to attach your hanger. Below is the Gripple system that uses a wire instead of a strip of galvanized hanger strap, but the process is exactly the same.

Powder Actuated Shot Fire Solutions

Watch the below video from Hilti a major manufacture of construction tools to see a version of this tool in action.

Hilti Powder-Actuated

Concrete Anchors

When powder actuated shot pins aren’t allowed you could use drilled anchors for concrete attachments. The benefit of power-actuated or drilled concrete anchors is your ability to locate them precisely where you want them from the same floor that the vertical hanger will be attached.

Expansion anchors will require the drilling of a hole for the insertion of the anchor. This process is a little more labor intensive then power-actuated shots and concrete inserts.

Beam Clamps

Just as the word implies this upper attachment clamps onto a structural steel beam for support of the ductwork. There are numerous types of beam clamps based on the type of structural steel support that it will attach to and the differing beam clamp designs by the various manufactures.

Badger Beam Clamps

The Gripple beam clamp shown in the video below is used with their proprietary hanger system that uses wires with a quick fastening, locking mechanism.

Gripple Beam Clamp
Hanger Upper and Lower Attachments
Beam Clamps

Wood Rafters

Various commercial construction projects and lots of residential projects are build out of wood. There are different ways of hanging duct from the wood structure, the easiest being a hanger strap nailed to the wood beam, but if your duct is large or if the local code requires something more stringent, there are other ways of hanging duct. Here is a detail that is at the more expensive end of the methods by which to hang from a wood structure, but it gives you an idea of hanging from wood beams.

Duct Hanger Wood Stud
Duct Hanger Wood Support

Metal Decking

There are many different manufactures that make hanger components. Here are various upper attachments for metal decks from Badger.

Badger No-Drill Metal Deck Hangers

Wood Form Concrete Deck

This upper attachment is used where wood forms are used for the laying of concrete. The upper attachment is nailed into the wood forms so that its held in place. The concrete deck will be poured encasing the upper attachment, which will be buried in the concrete providing a very rigid support. Then from the floor below the lower attachment will be attached to the embedded upper attachment. Watch this video to see how this is accomplished.

Vertical Support Members

The most common vertical supports are either sheet metal hanger strap (strips of galvanized sheet metal) or threaded rod. Hanger strap can be made in the shop from stocks of flat sheets or it can be purchased from vendors that sell rolls or bundles of pre-cut hanger straps.

The vertical support member is based on construction standards which take into consideration the size and weight of the duct.

All-Thread
Vertical Hanger Supports


Using all-thread is usually accompanied by a piece of angle iron or Unistrut horizontal support member for under rectangular ducts and some form of half or full angle ring for round duct.

1) Single Strap      2) Two Piece with Full Ring     3) Split Ring Hanger

1) Here a galvanized hanger strap is looped around the duct and fasten onto itself. This vertical support and lower attachment are one piece.

2) Here is a galvanized hanger strap attached to a lower attachment that is comprised of a full circumference sheet metal band.

3) This shows you the option of using a hanger strap or rod for the vertical hanger, and a split ring lower attachment support.

You can buy sheet metal hanger strap in rolls and cut them to length or order them from a fabrication shop pre-cut to the desired length.

Lower Attachment

The lower attachment is the portion of the hanger assembly that attaches to the duct. As shown above for round ductwork, this can either be a single strap of sheet metal, a full circumference ring or a split ring.

The lower attachment for rectangular duct can also use a continuous galvanized strap hanger wrapped under the bottom of the duct and fasten with sheet metal screws or rivets to the duct. For larger ductwork a vertical rod or hanger strap would be attached to a piece of angle iron, Unistrut or galvanized angle run horizontally under the duct.

Hanging Ductwork

Hanger Spacing

The distance between hangers is specified in the local code. The often cited reference for hanger requirements is SMACNA HVAC Duct Construction Standards. Hanger spacing in SMACNA is either every 4’, 5’, 8’ or 10’. Its best to use hanger spacing of 8’ or 10’ to maximize the span between hangers and reduce the amount of time for installing hangers.

As ducts get larger or spacing between hangers increases they will require a heavier gauge hanger or a thicker hanger rod.

For example, the following two ducts require very different vertical support materials at a 5 foot spacing interval.

Duct #1 – 60” x 16” requires a 1” wide 20 gauge strap or 3/8” rod

Duct #2 – 18” x 12” requires a 1” wide 22 gauge strap or 12 gauge wire

Things to Remember; The larger the duct or the spacing between hangers, the greater the strength of the hanger supports.

According to SMACNA, hangers are required on horizontal ducts within two 2 feet (0.61 m) of each elbow and within four 4 feet (1.2 m) of each intersection. Hangers are normally manufactured using galvanized steel strips or threaded steel rod, but in areas where there is a corrosive environment the use of electro-galvanized hangers provides additional protection.

The type and strength of the hanger is based on two important aspects;

  • The spacing between hangers
  • The size of the duct

The chart below shows the required vertical hanger support thickness required based on the half perimeter of the rectangular duct for the 8’ and 10’ spacing. See SMACNA table 4-1 for the 4’ and 5’ spacing requirements.

Rectangular Duct Hanger Chart-MEP
Rectangular Duct Hangers

Minimum Size Hanger Example;

Duct Size = 48” x 12”. Perimeter equals P= 48 + 12 + 48 + 12 = 120”

P/2 = 120”/2 = 60”

The chart below is for round duct minimum hanger sizes.

Round Hanger Chart
Round Hanger Chart

Hanger Length

If you’re using a software program for estimating than there will be a default length set in the database, usually 3 to 5 feet in length.

Hanger Capacity

The table below shows the maximum load (Lbs) a single vertical support member can support. (data from SMACNA Table 4-1) Starting from the bottom left we have a 1” x 22 gauge hanger strap that has a maximum load of 260 pounds, while all the way to the right of the chart we have a 1-1/2” 16 gauge hanger strap that has a maximum load of 1,100 pounds.

Single Hanger Maximum Load
Single Hanger Maximum Load

Trapeze Hangers for Multiple Ducts

The use of trapeze hangers will require a load calculation to determine what materials will be required to support the proposed load on the hanger and its upper and lower attachments. Trapeze hangers allow for the support of multiple ducts or a combination of ducts and pipes. A structural engineer maybe required to ensure that the structure can support the weight of the items supported on the trapeze hanger assembly.

Riser Supports

When a duct rises up through multiple floors or up within a shaft it will need to be supported at each floor or every other floor, with a piece of angle or other structural element that is capable of handling the weight of the riser. The riser support can be attached to the duct with sheet metal screws, rivets, bolts or welds. The riser support will often be attached to a concrete floor with anchors, a wood floor with screws, to structural steel with welds or bolts, or embedded into the concrete floor.

Make sure to include riser supports every floor or other floor, with at least a riser support every 12 to 24 feet based on the size and weight of the duct. Angles or channel can be attached to the side of the riser duct as shown in the images below.

Riser Supports
Duct Riser Supports

 

Riser Supports
Riser Supports

Wall Mounted Duct Supports

Duct running up an exterior wall will need some form of support to hold it in place. Depending on the height of the attachment some form of mechanical lift maybe required to allow a worker to safely make this connection to the structure.

Ductwork Riser Wall Supports
Ductwork Riser Wall Supports

Roof Duct Supports

Ducts are commonly run on roofs because of the lack of attic space or for convenience and ease of installation.

All roof ducts will need some form of support and attachment to the structure if required, unless Dura-blok’s or similar supports are allowed. Look at page 4 of this PDF for Dura-Blok supports that are commonly specified.

Roof Duct Support
Roof Duct Supports

Stack Supports

Exhaust stacks or boiler flues that extend above the roof could require some form of support. Here guy wire (aircraft cable) is used to keep the exhaust stack steady in windy weather.

Stack Supports
Stack Supports

Duct Stack Support – Guy Wires

Hangers in Commercial Construction

In new commercial construction projects the type of hanger you use will be based on the materials and methods of construction within the parameters of the local code. Are the floors poured concrete on metal Decking, if so you will have a system similar to the one shown in this video.

Construction Decking

The type of hanger you use will depend on the materials that you need your hangers to be supported from. Is the deck or floor above constructed of concrete, metal wood or some combination of materials?

Seismic Restraints

For those living in areas prone to earthquakes, equipment, pipes and ductwork might require seismic restraints. Based on the code in your area and the seismic zone that the property is located in; there are various seismic restraint requirements. Standard hangers are inadequate for seismic restraint, and will require additional reinforcement and support.

Duct Seismic
Duct Seismic

Duct Seismic

Hanging Duct
Hanging Duct using a Scissor Lift

Technology for Installing Hangers

On large commercial projects it’s possible that the contractor is using the latest in technology to install hangers. Trimble is a company that has specialized in GPS systems and has created the “Robotic Total Station” for laying out hangers in less time than traditional methods.

By importing the BIM (3-D Model) drawings into the Trimble program the system will identify the exact location on the jobsite for each hanger using laser technology. Watch the video below to see this technology in action.

The use of building information modeling (BIM) and its ability to export data for use in jobsite technology tools has increased field productivity rates far above existing manual methods. At the jobsite the instrument is positioned so it can be aligned with two building site control points. This allows the instrument to precisely locate the hanger location points using distances and angles matching the design drawings.

If installing hangers without the latest technology, you would need to breakout the old tape measure and find a control point to start from and measure to each hanger location. A control point is a reference point that allows you to start from a reliable spot in the building to measure from for accuracy. This would require that you have a set of printed detailed drawings that indicate the location of each hanger and its distance from some reference point in the building.

After you locate the location for each hanger, you’ll need to install the Upper Attachment, then the lower attachment hanger assembly. If you are using concrete inserts on metal decking, then you would mark the location on the deck using the laser guided tool for precise placement of the hanger. At that point you would punch a hole in the deck for the upper attachment using a special tool.

There are various upper and lower attachments based on the type of construction (new construction or retrofit), structural element to hang from and the code required hanger materials and methods. It’s important to know what your ductwork will be supported from, such as the concrete deck above, structural beams, wood rafters or joists.

Various Manufactures Hanger Systems

Below are some additional methods of hanging ductwork that are proprietary to the specific manufactures, such as Gripple and Ductmate.

Gripple “Fast Trak”

https://youtu.be/x_PBQDknKPU
Gripple

Ductmate Clutcher

Below is Ductmates® proprietary “Clutcher” hanger system. The Clutcher hanger system meets all of SMACNA’s upper and lower attachment requirements if installed per the manufactures installation guidelines.

The Clutcher by Ductmate


Gripple’s Duct Trapeze

Hanging Fiberglass Duct

Less commonly used is fiberglass ductwork. Here is a hanger system by Gripple that makes the hanging of fiberglass duct much easier than traditional methods. In this video the Gripple system competes side by side with the traditional method.

Gripple

Flexible Duct Hangers

Flexible ducts require a shorter distance between hangers because flexible duct lacks the rigidity to avoid excessive sagging. Flexible duct requires a maximum distance of 5 feet between hangers, but check your local code for more stringent requirements. According to SMACNA the maximum sag is 1/2” for every foot between hangers, this means that a 5 foot maximum span between hangers would allow a maximum sag of 2-1/2 inches.

Flexible Duct Hangers
Flexible Duct Hangers

Summary

The following is what we have learned in this lesson;

  1. Duct is hung with up to three separate hanger pieces; the Upper & Lower Attachments, and the vertical member.
  2. The upper attachment used depends on the structural component that it will be attached to.
  3. Powered actuated tools should not be used on concrete decks less than 4” thick or made of light-weight concrete.
  4. The choice of hangers is driven by the local codes and specified by the engineer
  5. Hangers are influenced by the size and weight of the duct.

Sheet Metal Field Installation Course

Resources

Dura-Blok Supports

Field Labor Crew Sizes

Chapter #5 – Field Labor Crew Sizes

The size of your labor crew depends on the project schedule, the amount of work required to be completed within that time frame, and the production rate of your crew.

Labor Crew Size
Labor Crew Size

It’s imperative that you understand the project schedule and the sequence of construction or phasing. In order to optimize your labor productivity you will want to maintain a consistent crew size, but this is not always possible as different phases or sequences of the project require varying amounts of labor.

You will need to determine how many workers are required at various stages of the project. Your crew size will vary depending on how much work is required at any point in the project within the window allowed by the project schedule.

Watch this video and pay attention to how many works are required at each stage of this small project requiring a helicopter.  From the warehouse workers who load the HVAC units onto the truck for delivery, to the workers on the ground at the building site who attach the new unit to the rigging cables and then to the workers on the roof who set the unit in place. How large was the crew at each stage of the process?

Helicopter Rig of a Rooftop Air Conditioner

It’s also possible that one or two of the crew members you see in the video are part of the Helicopter companies rigging and safety personnel. The fact that the HVAC units sit so far from the edge of the building makes it feasible to hire a helicopter than the oversized crane required to reach such far distances.

Factors Affecting Crew Size

  • Project Schedule (Duration)
  • Scope of Work per Scheduled Duration and Allotted Area (Quantity of Material & Equipment to be Installed)
  • Productivity Rate for Each Item to be Installed

Productivity Rate

How much work can get done in a day based on the project schedule and the project area available for your team? Projects are phased according to the most critical trade that needs access to the area. After reviewing the project schedule and determining the quantity of equipment and materials that you have to installed within that area you can determine the crew size with your productivity rate.

Your productivity rate is based on your company’s historical data from completed projects. The productivity rate will tell you how much of a certain item can be installed within a certain time frame. Units of measure usually include LF/Day (Linear feet / Day), Hours/Each, Lbs/Hr (Pounds per Hour).

The productivity values are collected from cost codes that your company uses to track various project tasks. The cost codes are broken down to be useful when analyzing future projects, such as keeping track of how long it takes to install round duct or small copper piping per foot, per hour.

Remember to review the chapter on Factors Affecting Labor Productivity.

How to Determine Crew Size
How to Determine Crew Size

Project Schedule

Let’s Look at various project durations as shown in column #1 in the above chart for a fictious project. We show a schedule of 5 days through 45 working days for a certain area of the project. If we have a certain amount of sheet metal to install within this area, and we know the quantity as shown in column #2 as 3,000 feet, and we have a productivity rate (column #3) from our historical labor feedback, this will determine the quantity of days (column #4) required to install this particular item. From here we can determine the crew size required as a simple formula as follows;

Construction Schedule
Construction Schedule

3,000 Feet / (50 Feet/Day) = 60 days / 5 Day Schedule = 12 Crew Members

3,000 Feet / (50 Feet/Day) = 60 days / 10 Day Schedule = 6 Crew Members

3,000 Feet / (50 Feet/Day) = 60 days / 15 Day Schedule = 4 Crew Members

3,000 Feet / (50 Feet/Day) = 60 days / 30 Day Schedule = 2 Crew Members (Item #6)

3,000 Feet / (50 Feet/Day) = 60 days / 45 Day Schedule = 1.3 Crew Members (Minimum 2 Crew)

As can be seen in the chart above, that from a 30 to a 45 day project schedule, the minimum required crew size is 2. As the project schedule gets longer a smaller crew size will be required to get the same amount of work done.

Weather

Extreme weather can be a cause for a restricted crew size as productivity is affected. Remember to review the chapter on those conditions which affect labor.

Consistent Crew Size

As mentioned above, it would be nice if you could maintain a consistent crew size, but this is unlikely as projects require varying amounts of field labor depending on the amount of task to be accomplished within the window of time allotted on the project schedule.

Crew Composition

Determining the mix of skilled and unskilled labor that will comprise the crew can be dictated by Union ratio requirements for union contractors and the availability of labor and skilled set required to accomplish the task at hand.

Having a method to pick your average crew size for the project will help you estimate the correct average hourly rate for the project. Most union labor rates use the Journeyman rate to determine all other rates.

Crew Size Summary
Crew Size Summary

Above and below we have inserted portions of the Labor tab of the MEP-Academy Estimating Spreadsheet where you pick the crew size and whether any of their time is at time an a-half (1.5x) or double-time (2x).

Sheet Metal Labor Rate Table
Sheet Metal Labor Rate Table

In the Sheet Metal Field Labor table above, you can see that there are various categories of labor including General Foreman, Foreman (#1), Journeymen (#2), and Apprentices (#3) of various levels of experience.

Step -1 Pick how many of each of the categories of field labor you want based on the total crew size determined above and the ratio of journeymen to Apprentices allowed by your local union if you’re a union contractor. The crew size will be indicated as shown in the example above by (#4), which in this case is a crew of 5 workers at a crew rate of $48.00/Hr. (#5)

Summary

Think of crew size in simple terms of you being told that you need to get a fence painted that is 300 feet long, the length of a football field. You figure based on your past experience of painting that you can paint at least 30 feet a day yourself. This would mean that if you were to do the project yourself and pocket all the money it would take you 10 days to paint the entire 300 feet of fencing.

300 feet / 30 feet per day = 10 Days

Now what if the owner said that he needed it painted in 5 days, and that he couldn’t wait 10 days. You have a choice, you could work two shifts a day yourself (16 hours a day or 60 feet/day), or you could hire another person to assist you.

30 feet per day / person x 2 Workers = 60 feet per day

300 feet / 60 feet per day = 5 days

Fence Painting
Fence Painting

The results would require two people work 5 days to complete the project per the owners schedule.

Project Schedule = 5 Days

Scope of Work = Paint 300 feet of fence in 5 Days. 300 feet/5 Days = 60 Feet / Day

Historical Productivity per Worker = 30 feet/Day per worker.

Workers Needed = Productivity Required (60 Ft/Day). (60 Feet/Day) / (30 Feet/Day/Man)

Now think of how many feet of sheet metal duct could be hung in a day instead of how many feet of fence you could paint in a day. Your companies historical data should be able to tell you how many linear feet of duct can be hung in a day based on differing size breakdowns.

Sheet Metal Field Installation Course

Sheet Metal Details and Specialties

Chapter #7 – Sheet Metal Details and Specialties

Most engineered drawings have a section for details, which allow for additional information to be provided. It is easier for the Mechanical Engineer to provide a detail showing exactly all the components required for a particular piece of equipment, duct specialty item or other building component that requires more information than what can be but on the plan view.

If the engineer was to put all the detail information on the building plan view, then this would make for a very messy and crowded drawing. It’s important that you review all the details as this is where cost impacts are usually incurred because of special requirements not identified anywhere else on the documents.

Utility Fan Exhaust Stack

Utility fan will often require that you install a length of sheet metal off the discharge side of the exhaust fan to ensure that the exhausted air doesn’t get entrained back into any of the building intakes. Often this stack will need independent supports like guy wires attached to a ring near the top of the exhaust stack and the other end of the wire attached to the roof structure. This will prevent the stack from being blown away on windy days.

Utility Fan Stack
Utility Fan Stack

Utility Fan Exhaust Stack

The two most common ways that Utility Exhaust fans support their discharge ducts or stacks are shown here. Above the discharge duct is support by the fan housing, while the exhaust stack (duct) shown below is support by the roof and has guy wires for additional stability during stormy weather. Of course, the detail below is going to have a greater cost impact. This is why its important to review the details.

Exhaust Fan Guy Wires
Exhaust Fan Guy Wires

Linear Diffuser Detail

Linear diffusers are used to provide a more pleasing look as envisioned by the architect, then the traditional square diffuser. Linear diffusers also cost more than the standard diffuser or grille. In this detail the engineer has also specified “Stainless Steel” duct bands (highlighted in yellow) which are more costly than the standard plastic pandit type. You would add this item to your sheet metal specialties page to include the additional cost. These bands hold the flexible duct securely in place to avoid becoming detached or so as to prevent leaking.

Linear Diffuser Details
Linear Diffuser Details

Linear Diffuser Detail

Acoustical Wall Penetration

When penetrating a wall that is acoustically rated to prevent the transmission of sound you would need to include the cost to sound proof your duct penetrating the wall. If you had a noisy room adjacent to a private office then you would want to make sure that none of the noise was transmitted from one space to the other.

Acoustical Sealing Duct Penetrations
Acoustical Sealing Duct Penetrations

Acoustical Sealing of Duct Penetration

Elbows at Diffusers or Registers

Engineers, certain facilities and various jurisdictions require that you install a 90 degree elbow at each piece of air distribution. This was most likely in response to projects where flex was installed incorrectly, causing kinks that reduced airflow to the space. To ensure proper airflow a 90-degree elbow is installed at the point of the diffuser or register as shown below. The traditional method is shown in the next detail where a flexible duct connection is used to attach the ductwork to the diffuser.

Flex with Elbow at Air Distribution
Flex with Elbow at Air Distribution

Air Distribution Connection Detail

There are several items that makeup a connection to a piece of air distribution. Each piece of air distribution should have a Balancing/Volume Damper to adjust the volume of air coming out of or into the air distribution. Some jurisdiction will allow a piece of flex duct to make the final connection between the duct and the air distribution grille.

Flexible Air Duct

Air Distribution Connection Detail

Steam Humidifiers

There are certain rooms that require that the RH (Relative Humidity) remain within a range, such as between 40% & 70% RH. A humidifier is installed in the duct to ensure proper humidity to the space. Since steam (moisture) is added to the air stream by the humidifier to maintain the required RH levels, the need for a non-corrosive duct material within a certain distance before and after the humidifier will be required, in addition to a drain.

As shown in the detail below, the engineer has specified that 4 feet before and 8 feet after the humidifier shall be constructed of welded stainless steel. Also, there are two access doors shown, one on each side of the humidifier to allow for easy viewing of the internal components of the humidifier.

Steam Humidifiers
Steam Humidifiers

 Roof Mounted Exhaust Fans

There are many types of roof mounted exhaust fans that require a curb to sit on. In addition there will be a Gravity Backdraft Damper to prevent outside air from being forced into the building under increased pressure from outside due to winds and storms.

A sheet metal transition is often required because the duct drop is a different size then that which connects to the exhaust fan. Check the vendors quote to make sure that the exhaust fan comes with the rood curb and BDD (backdraft damper). This also applies to exhaust and intake hoods that don’t have a motor, but strictly operate on pressure differentials.

Roof Exhaust Fan Detail
Roof Exhaust Fan Detail

CAV or VAV Detail

CAV (constant air volume) or VAV (variable air volume) air terminals may come with a sound attenuator as shown in the below detail. This is usually something provided by the air terminal manufacture, so you won’t need to price this as a piece of sheet metal, but you will need to confirm that the vendor has included them in their proposal. The sound attenuator (#3 below) muffles any noise coming from the CAV/VAV.

Also, if the inlet duct (#1 below) to the air terminal unit exceeds a certain distance then a requirement to increase the duct one size may be specified as shown in this detail. This is to ensure that the proper amount of air reaches the air terminal. There may also be a requirement to provide a high side flexible duct (#2 below) on the inlet side of the air terminal. When you look closely you will also see that there is a 90-degree elbow (#4 below) at the diffuser.

CAV Terminal Details
CAV Terminal Details

Remote Damper Operators

Used where dampers are concealed above inaccessible ceilings. The remote damper operator allows you to adjust the CFM (airflow) going through the duct by adjusting the damper position in the duct from a remote location like a wall or ceiling.

Remote Damper Operators
Remote Damper Operators

Sheet Metal Field Installation Course