Understanding HVAC Symbols

Chapter #5 – Understanding HVAC Symbols

In order to understand how to read HVAC drawings, you have to understand the road signs (HVAC Symbols). These vary from one engineer to the next, but there are some similarities that will help you figure the differences out. HVAC Symbols work like the road signs you are familiar with; they allow you to discern their meaning by a visual icon or image with very little use of words.

Street Signs
Street Signs

Without HVAC symbols the drawings would be crowded with words and sentences in an attempt to explain what is easily explained with a symbol.

There are symbols for all kinds of equipment, duct specialties, piping components and for all other trades. Symbols are the unspoken language in the construction trade. They convey meaning without words or in conjunction with abbreviations.

There should be a Legend of symbols on the mechanical drawings.

HVAC Symbols
HVAC Symbols Legend

You will find that there is no industry standard and that symbols can vary from one engineer to the next. Often if they are using the same CAD program and the symbols that are standard with the program then you will see similarities.

Don’t be confused by the variations of the same symbol from drawing to drawing. Focus on what the symbol is trying to convey.

Supply, Return & Exhaust Symbols

The following are used often throughout the mechanical drawings to indicate which type of air is in the ductwork, or which type of air distribution is being referenced.

The three most common being supply, return and exhaust. An “X” in a square or round shape is indicative of Supply Air, while a single Diagonal line indicates return air.

Supply Return and Exhaust Air Symbols
Supply Return and Exhaust Air Symbols

The following symbols indicate the type of air but also that of a riser duct. A riser duct is one that penetrates a floor. When the line is solid, it indicates that the duct is going up, and if the line is dashed, it indicates that the duct is going down.

Supply Return Exhaust
Supply Return Exhaust

Duct Risers in Shafts

In multi-story buildings it’s probable that you will have a shaft, which is usually a drywall enclosure that is fire rated to allow utilities, including HVAC ductwork to travel from one floor to another. When the ductwork leaves or enters the shaft it requires a fire damper or a combination fire/smoke damper, in order to prevent fires or smoke from traveling from one floor to another.

When looking at the shaft, you can determine which direction the ductwork is going by whether the lines are solid or dotted. Solid lines indicate that the ductwork is going up, and dashed lines (Hidden Lines) indicate the ductwork is going down.

Supply Return Exhaust Shaft
Supply Return Exhaust Shaft

Again, to distinguish which direction the above ducts are going, you only need to remember the rules governing hidden lines. The shafts on the left side show hidden lines (dashed lines) in the riser indicating that the shaft is headed downward, while the shafts on the right show solid lines indicating that these are duct risers going upward.

The above shows what a rectangular duct looks like in each case, while the below represents a round portion of duct that rises up and down. The round duct riser goes down on the left side as indicated by its dashed lines, and the other side goes up as indicated by the solid lines.

Round Duct Riser
Round Duct Riser

Air Distribution

Air distribution devices are used at the end of branch ducts or tapped onto the side of ducts to allow air out of or into the ductwork. Air distribution grilles, registers, diffusers and linears are chosen to allow for the proper dispersion of the air into the room based on acceptable noise criteria, throw distance and throw pattern. The arrows show the direction of the airflow. Supply shows the arrow exiting the air diffuser, while return and exhaust show the arrow pointing into the grille.

Supply Return Exhaust Grilles
Supply Return Exhaust Grilles

Supply Return Exhaust Grilles

he arrows show the direction of the airflow. Supply shows the arrow exiting the air diffuser, while return and exhaust show the arrow pointing into the grille.

Air Distribution
Air Distribution

Below is an example of what it might look like on the drawings. Note that different engineers will use different symbols. The below image shows the symbols indicating supply, return and exhaust air distribution devices.

Air Distribution
Air Distribution

Air distribution grilles, registers and diffusers will often have an acronym that matches an air distribution schedule on the drawing where the equipment is listed, which will define the make and model number for each piece & indicate the CFM.

Air Distribution Schedule
Air Distribution Schedule

 Ductwork Symbols

Most ductwork is either shown in single line or double line. There are also various types of ductwork that have their own symbols, such as flexible duct which is often shown as a squiggly line.

Symbols Flex Duct
Symbols Flex Duct

Ductwork can be internally lined for acoustical or thermal reason, that is for the reduction of sound transmission or for the reduction of heat loss or heat gain. This is usually indicated by a dashed line within a solid pair of lines.

Lined Duct
Lined Duct

In retrofit projects where the existing ductwork needs to be removed, the symbol that indicates this is usually some form of diagonal hash marks as shown below. Labor must be included in your estimate to remove this ductwork.

Duct Demo Symbol
Duct Demo Symbol

When existing duct is removed as shown above, but not all of the existing ductwork gets removed, there is a symbol that indicates a point at which the existing duct on one side of the line remains, while the duct on the other side of the line gets removed (Demoed)

Point of Demolition
Point of Demolition

When new ductwork is attached to existing ductwork, engineers will indicate this by using a point of connection symbol. The difference between the new ductwork and the old can also be determined by the type of line used. Lines that are dotted, dashed or thinly drawn are indicative of existing ductwork, while solid lines indicate new.

POC Ductwork
POC Ductwork

Routing ducts through buildings often require that they rise or drop to get around obstacles. This is indicated with an arrow and with a letter; R (Rise), D (Drop). As a sheet metal estimator you should add a couple of angles (45-degree elbows) or an offset fitting.

Duct Up and Downs
Duct Up and Downs

A special type of duct is used to prevent vibration and noise from transmitting down the ductwork from the source. The flexible duct section is used for equipment, but there are also special flex section used for seismic breaks.

Flexible Connection
Flexible Connection

Dampers

Fire Dampers

Fire dampers are shown as a dotted or solid line through the duct at the point where it penetrates the fire rated wall, accompanied by a solid diamond, square or other shape, often with the abbreviation FD (Fire Damper) as shown below.

Fire Damper
Fire Damper

Smoke/Fire Damper

This is a combination of two types of protective dampers, a fire damper, which protects against fires, and a smoke damper, which closes off the air by motorizing a damper closed.

Fire Smoke Damper
Fire Smoke Damper

Volume Dampers

The air in an HVAC system requires balancing in order that the air gets to the room in the quantity that the engineer intended. Volume dampers are shown as various straight lines perpendicular to the duct with a small handle.

Volume Damper Symbol
Volume Damper Symbol

Automatic Control Dampers

In order to control dampers automatically they need to have some form of actuator that will modulate, open or close to perform some function of the HVAC system.

Auto Control Damper
Automatic Control Damper

Miscellaneous Equipment

There will be miscellaneous pieces of HVAC equipment that will be inserted into the ductwork. Make sure to review what each symbol represents, as piece of equipment installed in the ductwork often requires transitions or special connections. As shown below this in-line coil which is larger than the ductwork will require two transitions.

Duct Mounted Coil

In-Duct Coil
In-Duct Coil Symbol

This next symbol represents a piece of equipment, in this case a heating coil as shown by the red outlined box in the image below, but it could be any type of coil. 

One of the ways to tell this is a coil is that there are pipes attached to it. Usually you will see two pipes entering the coil, but the engineer has chosen to show only one of the two pipes.

In Duct Heating Coils

Symbols for a Typical VAV Terminal & Ductwork

The image below is of a typical VAV (Variable Air Volume) terminal, this is a box connected to the ductwork that varies the volume of air based on the thermostats setting.

VAV Box
VAV Box

This symbol represents a piece of equipment, in this case a Variable Air Volume terminal box with a lined plenum. The VAV provides a variable amount of air to the diffusers based on the thermostat setting and current room conditions. This could also represent a CAV (Constant Air Volume) terminal box.

Symbols VAV Terminal
Symbols VAV Terminal and Ductwork

 Point of Connection (POC). This indicates where the new ductwork connects to the existing ductwork. Everything from this point forward is new, and everything before it is existing. Often, the new ductwork is shown in dark lines, while the existing is drawn lightly. Also, sometimes the (N) new ductwork includes an (N) before its size, to indicate its new.

POC Point of Connection
POC Point of Connection

As we learned above the “X” within a box refers to Supply Air, so this here is referencing a Supply Air Diffusers. This also shows that the SA (Supply Air) diffuser blows air in four (4) directions, as indicated by the arrows.

Supply Air Distribution Symbol
Supply Air Distribution Symbol

Volume Dampers are used to balance the system so that the correct amount of air (CFM) is provided through the diffuser to the space.

Volume Damper Symbol
Volume Damper

VAV (Variable Air Volume) Terminal. This is a piece of equipment purchased from a supplier, and manufactured by Titus, Metal Aire, Krueger, or similar. This VAV terminal will adjust the volume of air delivered to the space based on the demand of the thermostat.

VAV Terminal
VAV Terminal

Return Air Grille with a sound boot. This grille provides for air to return from the space back into the attic where it will make its way back to the system by the negative pressure created by the HVAC system. On the Return Air Grilles there is a sound boot, or a piece of lined sheet metal with an elbow to prevent noise from being carried to other spaces.

Return Air Grille Symbol
Return Air Grille

Thermostat

The thermostat controls the temperature setting for the room and controls the HVAC equipment. The symbol for a thermostat is often just a circle with a “T” inside as shown below. The thermostat shown below is controlling a VAV box.

Thermostat Symbol
Thermostat Symbol

Indication of Demolition

Items that are hashed out as shown in this picture indicate items of a retrofit project that need to be removed. This show two fans and duct that needs to be demoed and removed.

Demolition
Demolition

Equipment Tags

These are special symbols that identify the equipment by an acronym and a number. This helps tie together the equipment schedule that list all the equipment with tags that can be located somewhere on the floor plans to show where that piece of equipment resides in or on the outside of the building. This equipment tag (AC-1) represent Air Conditioner #1.

Equipment Tag
Equipment Tag

Drawing Notes

Drawings will use numbered tags that refer to a column of numbered notes that might be off to one side of the drawings. Putting the description or notes directly on the drawing next to the item could make the drawing messy and hard to read, it’s easier to put a small number next to the item that the note references.

Drawing Notes Symbols
Drawing Notes Symbols

Detail and Section View Symbols

As mentioned previously, these are drawing road signs that point you in the direction of another drawing where a detail or section view is available. These special symbols identify what other drawing that you need to review to understand in more detail the area referenced.

Detail and Section Symbols
Detail and Section Symbols

Next is Chapter #6 “Drawing Scales” to see how scales effect your takeoff and how to read scales including metric scales.

HVAC Mechanical Drawings

Chapter #4 – HVAC Mechanical Drawings

The mechanical drawings we will be dealing with are specifically related to the HVAC industry. Just like the other trades, the mechanical drawings have a specific purpose to their layout, so as to communicate the requirements of the project.

Typical drawings found in the HVAC Mechanical set of drawings could include some or all of the following;

  • Legend
  • Abbreviations and symbols
  • Equipment Schedule
  • General Notes
  • Specifications
  • Zoning plan
  • Demo
  • Floor Plan
  • Elevations
  • Section Views
  • Details
  • Schematics
  • P & ID Drawings
  • Control Diagrams

HVAC Mechanical Equipment Schedule

The HVAC equipment is shown on the Mechanical Equipment Schedule drawings. Here you will find the HVAC equipment such as Air Conditioners, Air Handlers, Fan Coil Units, Fans, Chillers, Cooling Towers, Pumps, Air Distribution, Expansion Tanks, Boilers, VFD’s (Variable Frequency Drives), Condensers and various other components of the HVAC system.

Mech Equip Schedule
Mechanical Equip Schedule

Zoning Map

This drawing shows how the HVAC zones are divided up. Each zone typically has its own controller or thermostat. You can see that the floor plan is separated with dashed lines indicating which areas or rooms share the same HVAC zone.

There are 20 zones on this zone map indicated as 4-1 through 4-20. These 20 HVAC zones could be served from one air handling unit. Each of the 20 zones can be served by a VAV (Variable Air Volume) terminal, that will vary the volume of air to the space based on the temperature of the room and the thermostat setting.

HVAC Zoning Layout Plan
HVAC Zoning Layout Plan

HVAC Floor Plan

The floor plan is a view from above, as if you were floating above the space.

This is where the sheet metal ductwork and HVAC Piping will be shown for each floor and area of the building. You might find that the HVAC Sheet Metal and the HVAC Piping are shown on separate drawings to allow for clarity and avoid having drawings that are congested and hard to read.

In addition to the floor plans for each floor in the building you will also have a Roof Plan that shows that portion of the HVAC system that is installed on the roof. Also, located on the plan view is a North arrow to provide building orientation (see plan view below for North arrow).

HVAC floor plan
HVAC Floor Plan

HVAC Detail Drawings

This drawing shows various HVAC details such as how equipment is supported, connected or provided with accessories.

HVAC Detail Drawings
HVAC Detail Drawings

HVAC Controls Drawing

Most commercial HVAC systems provide some aspect of controls automation, except for the most basic system that may just have stand-alone thermostats. Control system vary in their sophistication based on the owners need to monitor the system and the size of the HVAC system. Large central plants will often have some form of BAS (building automation system) that optimizes the energy usage and schedule of the system.

HVAC Control Drawings
HVAC Control Drawings

Plumbing Drawings

You may need to check the plumbing drawings to confirm if certain scope has been shown on those drawings. Engineers will often put the condensate piping from air conditioners on the plumbing drawings, or the gas piping for a Gas/Electric HVAC unit.

Plumbing Drawings
Plumbing Drawings

Since you are doing the Sheet Metal there might not be much if anything of your scope shown on the plumbing drawings except heater or boiler flues, but since you work for an HVAC company, it still falls under your company’s obligation to determine scope.

Plumbing HVAC Scope
Plumbing HVAC Scope

As shown in the above split image of the plumbing and HVAC drawings of the same area, the plumbing drawings have the gas piping that feeds the Gas Furnaces that are part of the HVAC scope of work. It’s important to clarify in your scope letter that you have excluded gas piping.

Structural Drawings

Looking at the structural drawings will sometimes provide you with information on supports for the mechanical equipment, ducts or piping. You can also determine how big the beams are and if there is enough room to possibly convert some of the more expensive rectangular ductwork into round duct.

Below is a small section of a structural drawings showing a large commercial buildings support beams. Just like other trades, the structural engineer uses means and methods to communicate information about the supports. The width and weight per foot of the beams are shown circled in red. The designation “W21 x 44”, means that the beam is 21 inches in depth and weights 44 pounds per foot. The “W24 x 55” is 24 inches in depth and weights 55 pounds per foot.

Structural Drawing
Structural Drawing

Demolition Drawings

When bidding on renovation projects there is a good chance that the existing HVAC system and ductwork will need to be removed or reworked. The engineer will provide a demolition drawing identifying which systems are to be removed or relocated. Typical anything with a hash mark through it will indicate an item to be removed, whether it’s a piece of equipment or a section of ductwork.

Drawing Revisions

When changes are made to drawings that have already been issued for bidding, the engineers will issue an addendum set of drawings for any updated changes made. These addendums usually cloud the areas on the drawings that have changed as indicated in the below image. In the image below the addendum is indicated as addendum #1 (see red circle around addendum symbol).

You would need to compare this addendum set to the original set of drawings to identify any changes that were made to the drawings. If you didn’t begin your takeoff or estimate on the previous set, then starting with this set of drawings would include the latest changes.

Several things to consider when working with an addendum set. First does the addendum set include a full set? Sometimes the engineer will only issue the drawings that have changes on them. This means that the addendum set may not be a full set. Check the list of drawings on the cover page or on the Architectural set. Be sure to identify all the drawings that you are bidding in your proposal.

Another thing to be aware of is that the engineers don’t always cloud the areas that have changed. This means that you will need to review the complete set for any changes that were made by the engineer but not clearly identified on the addendum set.

HVAC Floor Plans
HVAC Floor Plans

The drawing above also shows the equipment tags outlined by the blue squares. The first one is “RTU-1.1”, which stands for Rooftop Unit, but as can be seen in the drawing, this units is on the ground level. The next one is for “EF-1.3”, which is an Exhaust Fan.

Specifications on Drawings

Some engineers prefer to put their specifications on the drawings instead of issuing a book of specifications. Below is an example where the engineer put all of the specifications on the front page (M101).

Specification Drawings
Specification Drawings

Now click the link below for Chapter #5 “Understanding HVAC Symbols” to get an overview of the road signs on the drawings that provide information in pictographs.

Plan | Elevation | Section Views and Details

Chapter #3 – Plan, Elevation, Section Views and Details

You will need to understand how to read a set of engineered drawings before you can begin any sort of material takeoff or communication with others. This section of the course will explain how to understand and read the various elements of an engineered set of drawings.

Plan Views

The plan view is where all the floor plans are shown including other areas such as the Roof Plan.

Floor Plans

Each floor in the building will have its own drawing, unless the floor is too large to fit onto one drawing then there will be more than one drawing per floor.  The floor plan shows all the rooms, doorways, windows, stairways, elevators and whatever the Architect believes is pertinent information for an understanding of the floor plan. The Architects as indicated below as identified the following on this floor plan;

  1. Column number
  2. Distance between columns
  3. Room designation and size of room in square feet (SF)
  4. Room information chart (Schedule) listing each room number and its corresponding square feet.
  5. Match line indicates that there is a continuation of this floor plan on another drawing.
Floor Plan
Floor Plan – Plan View

Roof Plan

The roof plan is important as this is where some of the mechanical equipment is located. Roof exhausters, cooling towers, pumps, boilers, intake hoods and other HVAC equipment can often be found on the roof.

Roof Plan
Roof Plan

Looking at the roof plan we can see the following on the plans as indicated by the red circles;

  1. HVAC Equipment
  2. Key Plan as explained below
  3. Key notes that help explain what’s on the roof plan.
  4. The North arrow. This indicates the buildings orientation to the north pole.
  5. The drawing scale in bar format. This allows for an easy scale verification using any scale.
  6. The description of the plan view, in this case it’s indicated as being a “Partial” roof plan. This would give you an indication that there is another part of the roof not shown here.

Key Plan

The key plan identifies the area of the building that is being shown on the current drawing. For buildings that are too large to fit on one drawing at the standard scale of 1/8” or 1/4”, than the building floor plan needs to be shown on several drawings with match lines drawn to indicate where the drawing has been demarcated into separate drawing areas.

Plan Elevation Question
Key Plan

As can be seen from the shape of the shaded black portion of the Key Plan below, and the shape of the floor plan it is referring to, they are the same. So the Key Plan is a mini representation of the shape of the floor plan and the portion of the floor plan that this particular drawing refers to.

Also, the below drawing is the continuation of the floor plan shown above. The Match Lines line up to create a complete floor of the building as indicated by the Key Plan.

Floor Plan as identified by Key Plan
Floor Plan as identified by Key Plan

Multiple Floors

You have to visualize how each floor relates to each other. This will help you see the HVAC air ducts an piping risers that travel from the roof to the basement. By using the column lines on one floor, you can find the exact same place on the floor above or below. The yellow highlighted dotted lines align up one floors corner to the nest floor.

Floor Plans Stacked
Floor Plans Stacked

Drawing, Section View & Detail References

It would be difficult to provide the details of more intricate construction assemblies on the same drawing of the floor plan. This is where the Detail and Section view references clear up and better show the components and finish of these areas.

Drawing References
Drawing and Section References

The symbol helps you find the detail or section that is being referenced by the symbol. As shown in the example above the detail or section can be found on drawing “A-9”, Detail or Section #1. The arrows indicate the direction that you would be looking toward. The detail or section view will show you what you would see if you were standing there looking at the building components.

Detail Reference
Detail Reference

Detail #2 is found on Architectural drawing A-9 as shown by the reference above. The purpose is to show in greater detail the area that is outlined. The dimension shown are in metric.

Section View

This Section View comes from a cut of the plan view above. A section view is different than an elevation view. A section view shows a cut of some portion of the building, while an elevation view shows what the building exterior looks like on what of its sides, such as the north side of the building.

Plan View Example #2
Plan View Example #2

Above is the first floor plan view of a small commercial building with a section cut referenced as “C”. See this section cut below under the Section View.

Section View #2
Section View #2

Below is a partial section view of one portion of the interior indicated as Section View #7, as shown on drawing #A-10.

Section View #7
Section View #7

Building Section View

This shows the total section of the building along the cut. These views will help you determine the length of riser ducts that traverse from one level to another.

Elevation View General Layout
Elevation View General Layout

Elevation View

The elevation view shows the outside of the building from every orientation (North, South, East & West).

Elevation View
Elevation View

Detail Section View

Detail View
Detail View

Detail Views

The detail view provides a look at the building components that make up the area of reference. Details are drawn at a larger scale than the general drawings allowing for a better look at the methods of construction. On Architectural drawings, details could include doors, windows, eaves, while on Mechanical drawings they may show details of hangers, fire dampers, coil connections, equipment trim, and sheet metal duct seams and joints.

Mechanical Detail
Mechanical Detail

Now click the link below for Chapter #4 “HVAC Mechanical Drawings” to get an overview of these drawings.

Architectural Drawings

Chapter #2 – Architectural Drawings (How to Read Construction drawings)

You will need to understand how to read the Architectural drawings as they have information that can impact the cost of the Mechanical estimates. This section will cover some of the Architectural drawings and what to look for when bidding a Mechanical project. This section is not an extensive coverage of Architectural drawings, but is intended to provide you with the knowledge on what to look for when bidding the mechanical portion of the project.

Architectural Drawings

You should be able to understand how to read the basic information on the Architectural drawings as these drawings are the foundation upon which all the other trades are drawn. The Architect designs the building, while the structural engineer figures out how to support the design. The Architectural design set may include the following drawings.

  • Cover Sheet
  • General Notes, Drawing Index, Abbreviations, Code Info
  • Plot Plan (site plan)
  • Foundation Plan
  • Floor Framing Plan
  • Floor Plans
  • Roof Plans
  • Reflected Ceiling Plan
  • Window and Door Schedules
  • Wall Sections
  • Elevation Plan
  • Details and Section Views

Architectural Floor Plans

You can use the Architectural floor plans to identify the name and use of a room. The drawings will show the room layout with walls, doors and windows. Each room should be identified by a room number and room name.

If you’re not familiar with reading drawings then you’ll need to study the background carefully to discern the various ways in which building items are represented on the drawings. Just like in real life the first one or two letters of the room number will indicate the floor its located on, as in this example here all the room numbers begin with 1, so we can assume this is the first floor.

Drawing layout
Architectural Drawing layout

As can be seen in the above image of the bathroom area taken from the floor plan of an Architectural drawing, there are symbols for each of the bathroom fixture. We have highlighted all the walls in yellow to make it easier to see each room.

Reading a set of construction drawings requires that you learn basic drafting guidelines and the symbols used to convey meaning, much like a traffic sign tells you what to expect up ahead.

Reflected Ceiling Plan

The reflected ceiling plan shows you what type of ceiling is used in each room. Below is an example of a small portion of a building, showing the type of ceiling used. With each set of architectural drawings there will be a legend for the ceiling types used in the set. (See legend below)

Reflected Ceiling Plans
Reflected Ceiling Plans

The below reflected ceiling plan identifies the type of ceiling, light fixtures used and the height (yellow highlight) of the ceiling in each room. Looking at the reflected ceiling plan above you can also see that Supply (blue highlight) and Exhaust (green highlight) grills are shown on the ceiling in addition to the lights.

Reflected Ceiling Plan Legend Example
Reflected Ceiling Plan Legend Example

The HVAC system ductwork and air distribution grilles are overlaid on the reflected ceiling plan. By looking at the reflected ceiling plan below and the legend above you can identify the type of ceiling that each air distribution is set into.

For any volume damper hidden above a hard lid ceiling you will need a remote damper operator or an access panel to provide a means for adjusting the damper. The remote damper operator allows you to adjust the volume damper without needing to remove a piece of the ceiling (see Sheet Metal Specialties).

HVAC shown on Reflected Ceiling Plan
HVAC shown on Reflected Ceiling Plan

Fire Rated Corridors

In large commercial buildings you will often find that the corridors are fire rated to protect the occupants in case of a fire. There are several common methods of rating the emergency exit ways. Fire rated corridors are important to the HVAC industry because under certain circumstances when a supply, return or exhaust duct penetrates the fire rated assembly, which could be the wall or ceiling, a fire or fire/smoke damper could be required.

Fire Rated Corridors
Fire Rated Corridors

The corridor or emergency pathways are rated to allow sufficient time for the occupants to evacuate the building in the case of a fire. The rated corridor or pathway will prevent the fire from spreading long enough for the occupants to get out. The area shown in red above is the emergency pathway or corridor that is fire rated.

Fire Rated – Slab to Slab System

In this method of fire rating the exit way, the use of rated walls extending from the floor all the way to the deck above provide protection. There is no rated ceiling, as the deck above is considered a fire barrier.

Fire rated walls - slab to slab
Fire rated walls – slab to slab

Fire Rated – Tunnel System

This version of a fire rated exit way is constructed in a tunnel configuration that’s fire rated for the purpose of protecting the occupants during an emergency situation. With the tunnel rated system if you penetrate the rated tunnel ceiling to install a supply, return or exhaust grille you will be required to install a fire damper or a fire/smoke damper to maintain the fire rated construction.

Fire Rated Tunnel Corridor System
Fire Rated Tunnel Corridor System

Here are the two most common fire rated construction methods side by side for comparison.

Fire Rated Construction Types
Fire Rated Construction Types

Detail Drawings

In order to show how certain aspects of the construction is to be built in greater detail each trade will provide a detail drawing. These drawings show various components of construction in greater detail. This allows the installers a more accurate detail of what the engineer expects in the way of material and methods in a visual format as opposed to the specifications.

Architectural Sheet Test-Question
Architectural Detail Drawing

Now click the link below for Chapter #3 “Plan, Elevation, Section Views and Details” to get an overview of these drawings.