Sunday, June 15, 2025
Home Blog Page 25

Daylighting for Health and Energy Savings

0
Daylighting for better health and energy savings
Daylighting for better health and energy savings

Daylighting for Health and Energy Savings. In this article we’ll discuss the many benefits of daylighting including improved health and energy efficiency. However, we’ll cover why it’s important to design and implement daylighting strategies carefully, considering factors such as building orientation, climate, and occupant needs, to ensure optimal performance and maximum benefits. 

If you prefer to watch the video of this presentation, then scroll to the bottom or click on the following link. Daylighting for Health and Energy Savings

In the U.S. the location of windows is important for implementing daylight saving strategies while preventing excess heat gain in summer months. According to the Department of Energy (DOE), windows that are located on the South side of a building provide the most light in winter months, while minimizing direct sunlight during the summer to keep the interior cooler. Windows located on the north of the building are also beneficial for bringing in natural light with little glare and little summer heat. Orientation of the building should be optimized to avoid windows on the east and west sides of the building as they don’t work as well for daylighting because of excess heat gain and glare during the summer months. 

How to Increase Daylighting while reducing glare

To increase daylighting while reducing glare, you can implement various design strategies and use appropriate materials. Here are some suggestions:

Use light-colored or reflective surfaces: Light-colored walls, ceilings, and floors can help distribute natural light more effectively throughout a space. Reflective materials, such as glossy finishes or mirrors, can bounce light deeper into the room.

Install windows with appropriate glazing: Consider using windows with glazing that reduces glare while allowing ample natural light to pass through. Low-emissivity (Low-E) coatings on window glass can help to control the amount of visible light and heat transmitted while minimizing glare.

Utilize shading devices: Implement window treatments like blinds, shades, or curtains that can be adjusted to control the amount of sunlight entering a room. Tilted blinds or louvers can redirect light towards the ceiling, creating a softer, indirect illumination.

Incorporate light diffusers: Light diffusers, such as frosted glass, prismatic panels, or light shelves, can scatter and disperse natural light, reducing direct glare while still maintaining a high level of daylighting. They help to create a more evenly distributed illumination.

Optimize interior layout and furniture arrangement: Arrange workstations or seating areas in a way that allows natural light to reach deeper into the space. Avoid placing desks or seating directly in the path of strong sunlight to minimize glare.

Use adjustable lighting systems: Combine artificial lighting with daylighting by incorporating adjustable lighting systems. Dimmable lights or those with occupancy sensors can help balance artificial and natural light levels throughout the day.

Consider exterior shading elements: Exterior shading devices such as overhangs, awnings, or fins can effectively block direct sunlight and reduce glare. These elements can be designed to allow low-angle sunlight to enter the space while blocking high-angle sunlight.

Implement light redirecting techniques: Light redirecting films or glazing can be applied to windows to diffuse and redirect sunlight, reducing glare while maintaining a high level of daylighting. These films can help distribute light more evenly and prevent harsh reflections.

Use daylighting analysis tools: Computer simulations and daylighting analysis tools can help optimize the design by modeling how natural light will interact with the space. These tools can assist in identifying potential glare issues and refining the design to maximize daylighting while minimizing glare.

Remember, the specific strategies to implement will depend on factors such as the building’s orientation, location, and the desired level of daylighting. Working with a professional architect or lighting designer can provide more tailored solutions to address your specific needs.

Health Benefits of Daylighting

Daylighting, which refers to the use of natural light to illuminate the interior of buildings, has been shown to have several health benefits. Here are some of the ways in which daylighting can be good for your health:

Patient Rooms: In the design of hospitals there is a requirement that all patient rooms are provided with a window, as research has shown that patients exposed to natural daylighting have faster recoveries with less medication.

Reduces stress and improves mood: Exposure to natural light has been linked to increased production of serotonin, a neurotransmitter that helps regulate mood. Exposure to natural light has been shown to reduce stress and anxiety levels. This is because natural light can help regulate your body’s levels of the hormone cortisol, which is often referred to as the “stress hormone.”

Improves sleep and Mental Clarity: Exposure to natural light during the day can help regulate the body’s circadian rhythm, which is the internal “clock” that helps regulate sleep and wake cycles. This is because natural light helps your body produce the hormone melatonin, which is important for regulating sleep. This can lead to better sleep at night, which is essential for overall health and well-being.

Enhances vision: Natural light is typically much brighter and more evenly distributed than artificial light, which can help reduce eyestrain and improve visual acuity, making it easier to see details and colors.

Increased comfort: Spaces that are well-lit with natural light are typically more comfortable and enjoyable to work in than those that are poorly lit with artificial light. This can help improve morale and motivation.

Increased Productivity and Reduced absenteeism: Studies have shown that workers in spaces with natural light are less likely to take sick days, and that people who work in well-lit environments are more productive and make fewer errors than those who work in poorly lit spaces.

Saving Energy with Daylighting

Daylighting can save energy by reducing the need for artificial lighting and by decreasing the amount of energy needed to cool a building. Here are some ways in which daylighting can help save energy:

  1. Reduced need for artificial lighting: By incorporating daylighting strategies such as windows, skylights, and light shelves, natural light can be used to illuminate the interior of a building during daylight hours. This can reduce the need for artificial lighting, which is typically one of the largest energy consumers in a building.
  2. Use of daylight-responsive lighting controls: Daylight-responsive lighting controls can be installed to automatically adjust artificial lighting levels in response to the amount of natural light in a space. This can help ensure that artificial lighting is only used, when necessary, further reducing energy consumption.
  3. Lower cooling costs: Traditional electric lighting can produce significant amounts of heat, which can increase cooling loads and energy consumption. By using natural light instead of electric lighting, less heat is generated, which can reduce the need for air conditioning and lower cooling costs while saving energy.
  4. Improved thermal comfort: Daylighting can also improve thermal comfort by reducing temperature fluctuations and creating a more pleasant and comfortable environment. When occupants are comfortable, they are less likely to adjust the thermostat or use additional energy-consuming devices to regulate the temperature. 

Here are the basic steps of how daylighting works:

  1. Sunlight enters the building through windows, skylights, or other openings in the building envelope.
  2. The light is then diffused and dispersed throughout the space using various materials, such as light shelves, louvers, or prismatic glass, to reduce glare and create a more even distribution of light.
  3. The daylight is then directed to where it is needed most, such as workstations, classrooms, or living spaces, using reflective surfaces and other design features.
  4. To maximize the benefits of daylighting, it is important to control the amount of light entering the building, especially during times of the day when the sun is most intense. This can be achieved through shading devices, such as blinds or exterior shading structures, or using automated lighting controls that adjust artificial lighting levels in response to the amount of natural light present.

How daylighting effects student performance

Daylighting can have a positive impact on student productivity in several ways:

In addition to the health benefits mentioned previously, here are some further notes as it relates to students and natural daylight.

Improved academic performance: Studies have shown that students who learn in well-lit environments perform better academically than those who learn in poorly lit spaces. This may be due in part to the fact that natural light can help improve cognitive function, including memory, attention, and decision-making. 

Reduced behavioral issues: Natural light has been linked to reduced stress and improved mood, which can help reduce behavioral issues in the classroom. When students are in a better mood and less stressed, they are more likely to be engaged in their work and less likely to exhibit disruptive behavior.

Reduced absenteeism: By creating a more comfortable and healthy learning environment, daylighting can help reduce absenteeism and improve overall attendance rates. When students are exposed to natural light during the day, it can help keep them alert and awake, which can reduce absenteeism and improve attendance.

Overall, daylighting can have a positive impact on both physical and mental health, making it an important consideration when designing and constructing buildings. By creating a comfortable and healthy work environment, daylighting can help employees feel more engaged, alert, and productive. Employers can potentially improve the bottom line by increasing productivity and reducing absenteeism and turnover By incorporating daylighting into building design. Daylighting can be an effective way to save energy in buildings by reducing the need for artificial lighting and decreasing cooling loads. By incorporating daylighting strategies into building design, building owners and managers can potentially reduce energy costs and environmental impact while creating a more comfortable and healthy work or living environment.

Daylighting for Health and Energy Savings

How to Size Plumbing Water Pipes using Fixture Units

0
How to size plumbing water pipes using fixture units

How to size plumbing water pipes using fixture units. Plumbing codes use various methods to determine the size of the water piping feeding a building. One of those methods is to use Fixture Units. To figure water supply fixture units, you need to calculate the demand load that plumbing fixtures will place on a water supply system. Here are the 14 steps required to size domestic water mains and distribution piping along with how to determine fixture units and the volume of water required.

If you prefer to watch the video of this presentation than scroll to the bottom or click on this link. How to Size Plumbing Water Pipes using Fixture Units

Step #1 – Figuring Total Water Supply Fixture Units (WSFU’s)

Identify the different types of plumbing fixtures that will be connected to the water supply system. Examples of common fixtures include toilets, sinks, bathtubs, showers, dishwashers, and washing machines. We’ll use a 3-story office building for our example. Here we show that each floor has four water closets, three urinals, and three lavatories.

Plumbing fixture unit example using a 3 story building
Plumbing Water Supply Fixture Unit Values for Plumbing Fixtures
  • Determine the water supply fixture unit value of each type of fixture. Water supply fixture unit (WSFU) is a measure of the flow rate of water through a specific fixture. The WSFU of a fixture can be found in the plumbing code or by consulting a plumbing engineer. Here we show several different codes and the various tables they use for fixture unit values. 

Each code will have a procedure for calculating the required flow rates based on the type and quantity of fixtures. Here we use the 2021 International Plumbing Code Table E103.3(2) for our example. The table shows that a public “Lavatory” has 1.5 fixture units, and a public “Urinal with a 3/4” flushometer valve” has 5 fixture units, and a public “Water Closet with flushometer valve” has 10 fixture units.

  • Multiply the WSFU of each fixture by the number of fixtures of that type. This calculation will give you the total fixture units (WSFUs) for each fixture type. 

For our example, there are three lavatories per floor, times three floors, which equals a total of 9 lavatories and based on 1.5 WSFU each, there would be a total of 13.5 fixture units for the lavatories. 

There are also a total of 9 urinals with a value of 5 fixture units each. The total fixture units for all the urinals are 9 times 5 = 45. Then there are 4 water closets per floor times three floors, for a total of 12 water closets. The WSFU for a water closet with a flushometer valve is 10, which would give us 12 x 10 = 120 fixture units.

  • Add up the WSFUs for all fixtures in the building or plumbing system to get the total WSFUs for that system. This will include adding up the total fixture units for each branch and riser. What we haven’t considered is any water flow demands for cooling towers, RO systems, Process Equipment, or landscaping. The plumbing engineer will need to work with the other trades to determine their needs for water. In our example we have a total of 13.5 WSFU’s for lavatories, 45 for urinals and 120 fixture units for water closets, for a total of 178.5 fixture units.
Total Plumbing Water Supply Fixture Units (WSFU) for 3-Story Example
Total Plumbing Water Supply Fixture Units (WSFU) for 3-Story Example

Step #2 – Determine the Water Flow (GPM) or (L/m)

Determining the water flow involves finding the total Water Supply Fixture Units in the very left column of IPC table 103.3(3), then moving along that row to the intersection of the demand column for “Supply Systems for Flushometer Valves”. The Total Fixture units are close enough to 180 so the use of this row is fine. This gives us a water flow of 85.5 GPM or 323.6 liters per minute.

Checkout these Plumbing Fixtures here
IPC Table 103.3(3) - Converting Water Supply Fixture Units to Water Flow in GPM
IPC Table 103.3(3) – Converting Water Supply Fixture Units to Water Flow in GPM

Step #3 – Obtain Minimum Daily Static Pressure Available

The available static pressure in psi or kPa at the water meter or source of water supply is provided by the City or local water authority. The minimum pressure is used in the calculations to ensure that during peak water usage season, pressure is available to operate the most demanding fixture.

Peak water usage usually occurs in summer when landscaping systems are maximized, and water-based cooling systems are utilized at their peak. It is essential that sufficient water pressure be available to overcome all the plumbing water system losses due to friction and elevation so that plumbing fixtures operate properly. For our example we’ll use 70 psi or 482 kPa.

Step #4 – Pressure Loss due to Building Height

To get the flow of water needed for the building there needs to be enough pressure left over after subtracting for all of the losses that occur due to various reasons, the first is the height of the building. Water exerts a pressure of 0.433 pounds per square inch for every 1 foot in height, or 9.81 kPa per meter.

Steps for Calculating Main Domestic Water Piping Size
Steps for Calculating Main Domestic Water Piping Size

The pressure coming from the city will be reduced by the loss occurred from this column of water sitting in the pipe risers feeding the building. In our example (see image above) the building is three stories high and has a 35 foot (10.6m) riser. To determine the loss of pressure from this column of water the following equation is used.

Riser Height in Feet (Meters) x Pressure loss per Foot (Meter)

35 Feet x 0.433 = 15.2 psi or

10.6 meters x 9.81 kPa = 105 kPa

Step #5 – Minimum Pressure required at Remote Fixture

This is to ensure that the fixture has enough pressure to operate properly. Each fixture requires different amounts of pressure to operate, so it’s important to pick the remote fixture that requires the greatest pressure to produce a flow.

IPC Table 604.3 for Minimum Pressure Requirements.
IPC Table 604.3 for Minimum Pressure Requirements.

Using IPC table 604.3 the siphonic water closet with a flushometer valve needs 35 psi or 241 kPa for proper operation.  

Checkout these Plumbing Fixtures here

Step #6 – Pressure loss through water meter

The friction loss or pressure loss through the water meter can be found from the manufacturer of the water meter. In our example we’ll use 6 psi or 41 kPa for the pressure loss through the meter.

Step #7 – Pressure loss through Backflow Preventer

The use of a reduced pressure backflow assembly (RPZ) is to prevent dirty water from reversing flow and contaminating the clean water supply. If required then the pressure drop needs to be included in the calculation for total pressure loss. In our example the pressure drop is 4 psi or 28 kPa.

Step #8 – Pressure loss through Pressure Regulating Valve

The IPC restricts excessive water pressure by requiring a pressure regulating valve when the pressure exceeds 80 psi (552 kPa). The reason is to reduce the incident of water hammer, reduce the excessive loss of water from pressure relief valves, and for the protection of equipment and fixtures. Since the maximum water supply in our example is less than this, there is no need for a PRV.

Step #9 – Total Pressure required for Operation

Add up all the pressure losses and the required minimum water pressure at a remote fixture with the highest requirements. Adding Steps #4 through #8 in our example equals 60.2 psi or (415 kPa). This is the total pressure required for proper operation, but not including the required pressure drop caused by the water flowing through the pipe and fittings.

Plumbing Water Pipe Size Calculation Steps
Plumbing Water Pipe Size Calculation Steps

Step #10 – Pressure available for Friction Loss

Subtract all the losses in Step #9 from the minimum available pressure in Step #3. If the available pressure is 70 psi or 482 kPa, then our calculation looks like this. 70 psi – 60.2 psi = 9.8 psi, or 482 kPa – 415 kPa = 67 kPa, this is the amount of pressure left over for the resistance to flow that is needed to move the required GPM or LPM to the most remote fixture.

Step #11 & 12 – Total Developed length of Piping

This is the developed length of the water piping between the water source and the most remote fixture times 1.5 to account for pressure loss through fittings and valves. Fittings and valves add 50% to your total length, but this could vary based on design. In the example here there is a total of 140 feet or 42.6 meters from the water source to the most remote fixture. The calculation would be 140 feet x 1.5 = 210 feet, or 42.6 meters x 1.5 = 63.9 meters of total developed length.

If you know the exact amount of fittings and valves then table E103.3(6) in the IPC could be used to determine the equivalent length for each size and type of fitting or valve.

Step #13 – Determine the Friction Loss per 100 Feet

This calculation determines the leftover pressure in the system that can be used to overcome the pressure loss due to friction in the pipes and fittings. Step #10 shows that there is 9.8 PSI or 67 kPa for friction loss.

The calculation would be (9.8 psi/210feet) x 100 = 4.7 psi/100 feet

Step #14 – Determine Size of Water Service Pipe

This is where the size of the main is determined using the information that we have put together so far.

Using IPC Table 103.3(3) for Friction Loss in Smooth Copper Tubing
Using IPC Table 103.3(3) for Friction Loss in Smooth Copper Tubing

Using Figure 103.3(3) we enter the total GPM of 85.5 and our allowable pressure drop of 4.7 psi/100 feet and they intersect just above the 2” pipe line, so to be safe we’ll specify a 2-1/2” or 65mm pipe.

Plumbing Water Supply Fixture Unit Calculation Totals for Water Pipe Sizing
Plumbing Water Supply Fixture Unit Calculation Totals for Water Pipe Sizing

If we found out through our analysis that there wasn’t enough water pressure from the city to overcome all of the pressure losses and provide the minimum required pressure at the most remote plumbing fixture, then a booster pump would be considered.

How to size Plumbing Water Pipes using Fixture Units

Skilled Workers for Contractor Success

0
See why Skilled workers are important for contractor success.
See why Skilled workers are important for contractor success.

Skilled workers for contractor success. This is the fourth article in our series on what it takes to create and sustain a successful construction contracting company. See why skilled Construction workers are one of the key factors for creating a successful construction company.

If you prefer to watch the Video of this presentation scroll to the bottom or click on this link. Skilled Workers for Construction Success

Skilled construction workers are important for the following reasons:

Quality of Work

Skilled construction workers have the necessary training, experience, and knowledge to produce high-quality work. They understand the technical aspects of their trade and can perform complex tasks that require precision and attention to detail. They know how to read and interpret plans, use the right tools for the job, and ensure that everything is built to code. As a result, their work is more likely to meet or exceed industry standards and is less likely to require costly rework. 

Safety

Construction sites can be dangerous, with heavy machinery and materials, working at heights, and other potential hazards that could cause injury or even death. Skilled construction workers are trained in safety procedures and know how to mitigate hazards and use equipment correctly. They are less likely to cause accidents on the job, which can result in injury or damage to property. This helps to ensure that everyone on the job site remains safe and healthy.

Efficiency

Skilled construction workers can work more efficiently than unskilled workers. They know how to use their tools and equipment effectively and can complete their work quickly without sacrificing quality. This can help to reduce the overall time and cost of a construction project.

Problem-solving

Skilled construction workers can identify and solve problems that may arise during the construction process. They have the knowledge and experience to troubleshoot issues and come up with creative solutions that keep the project moving forward and on schedule. 

Improved Profitability

The use of skilled workers ensures that work is completed on time, while avoiding rework which effects the profitability of your business and reputation in the construction industry.

Overall, skilled construction workers play a crucial role in the success of any construction project. They bring expertise, quality, safety, efficiency, and problem-solving skills to the job site, helping to ensure that the project is completed on time, within budget, and to a high standard of quality.

Contractor Success Series

  1. Estimating and Budget for Contractor Success.
  2. Strong Leadership for Contractor Success.
  3. Good Project Management for Contractor Success
  4. Skilled Workers for Contractor Success
  5. Construction Safety for Contractor Success
  6. Technology in Construction for Contractor Success
  7. Financial Stability for Contractor Success
See why Skilled Workers are important for Contractor Success.

Good Project Management for Contractor Success

0
Contracting Success Series Good Project Management
Contracting Success Series Good Project Management

Good Project Management for Contractor Success is the third article in our series on what it takes to create and maintain a successful contracting company. Good construction project management is essential to the success of any construction company or project. It helps ensure that the project is completed on time, within budget, and to the required quality standards.

If you prefer to watch the video of this presentation then scroll to the bottom or click on the following link. Good Project Management for Contractor Success

Here are seven reasons why good construction project management leads to success:

1) Planning

Effective project management involves careful planning of every aspect of the construction project, from the initial design to the final construction phase. This helps ensure that the project is completed on time, within budget, and to the required standards.

2) Resource Management

A good construction PM can effectively allocate resources such as labor, materials, and equipment to ensure that they are used efficiently. This can help to reduce costs and increase productivity, which ultimately leads to a successful project that is completed on time and within budget.

3) Effective Communication

Effective communication is critical to any construction project, and a good project manager will ensure that all stakeholders are kept informed throughout the project. This includes the client, engineers, contractors, suppliers, and workers. Clear communication helps to prevent misunderstandings and delays, which can cause costly project overruns.

4) Clear Project Goals and Objectives

A good PM sets clear goals and objectives for the project. This helps to ensure that everyone is working towards the same goal and that the project stays on track.

5) Risk Management

Effective project management also involves identifying and mitigating risks that could impact the project’s success. This includes identifying potential delays, cost overruns, and quality issues and developing contingency plans to address them, including all workers are aware of safety protocols. This helps to minimize the impact of any unforeseen events and ensure that the project is completed on time and within budget.

6) Quality Control

Good project management includes quality control processes to ensure that the project is completed to the required quality standards and meets the requirements of the specifications and contract. This helps to avoid costly rework and ensures that the final product meets the client’s expectations. This includes inspecting materials and workmanship and ensuring that all work meets the required specifications.

7) Timely Delivery

A construction PM must ensure that the project is completed on time. This requires careful planning, scheduling, and monitoring to ensure that all tasks are completed on schedule. Delays can result in increased costs, lost revenue, and damage to the reputation of the contractor.

In summary, good construction project management is crucial to the success of any construction project or company. It helps to ensure efficient use of resources, effective communication, clear project goals and objectives, risk management, and quality control. Good project management helps to prevent delays while completing projects on time, reducing costs, ultimately leading to a successful project outcome.

Contractor Success Series

  1. Estimating and Budget for Contractor Success.
  2. Strong Leadership for Contractor Success.
  3. Good Project Management for Contractor Success
  4. Skilled Workers for Contractor Success
  5. Construction Safety for Contractor Success
  6. Technology in Construction for Contractor Success
  7. Financial Stability for Contractor Success
Good Project Management is one key factor in Contractor Success