Friday, June 13, 2025
Home Blog Page 30

VRF Heat Recovery vs VRF Heat Pump

0
VRF Heat Recovery vs Heat Pump

VRF Heat Recovery vs VRF Heat Pump. VRF stands for Variable Refrigerant Flow, a method of varying the volume of refrigerant circulated in the system in relation to demand. As demand drops so does the volume of refrigerant circulated by the compressors. The compressor can slow down and pump less refrigerant to meet the current demand of the system. We’ll explain the differences between a VRF Heat Recovery System and a VRF Heat Pump.

If you prefer to watch the Video of this presentation than scroll to the bottom or click on this link. VRF Heat Recovery vs VRF Heat Pump.

One of the big differences between a VRF Heat Pump and Heat Recovery system is that with a VRF Heat Pump system all the units must be in the same mode. Either cooling or heating.

VRF Heat Pump with Individual Zones

As seen here this one outdoor unit can feed many indoor units, but all the indoor units need to be in the same mode, such as heating as shown here, or all in cooling. With a VRF Heat Pump system if each zone or office wanted to control whether to heat or cool their space, then each would require their own outdoor unit.

Here we have an Executive in Office #1 wanting heating, while the second office wants cooling, each indoor fan coil will require a separate outdoor unit, and the third office is also calling for cooling and will have their own outdoor unit.

To reduce the number of outdoor units, the engineer will group together those zones that have similar load profiles. So, indoor Fan Coil #2 and #3 have similar load profiles, so we can get rid of one of the extra outdoor units and its piping and connect Fan Coil #3 together onto the outdoor unit #2, this saves on outdoor units.

VRF Heat Pumps with Consolidated Zoning
VRF Heat Pumps with Consolidated Zoning

Now whenever Fan Coil #2 and #3 switch modes of operation they will always be in the same mode as they’re on the same outdoor heat pump system, as shown here now in heating mode together, while the outdoor unit #1 can be in any mode separate from the other system.

The benefit of using a VRF Heat Pump system over the traditional split system heat pump is that you have inverter compressor and multiple indoor fan coils all working together to achieve a lower energy consumption. 

VRF Heat Recovery vs VRF Heat Pump (Heat Recovery System with 3-Port Branch Controller)
VRF Heat Recovery vs VRF Heat Pump (Heat Recovery System with 3-Port Branch Controller)

The disadvantage when we look at the VRF Heat Pump versus the VRF Heat Recovery as shown here is that if we install a 3 port Branch Controller Box and  connect the refrigerant piping to the outdoor unit, we can then  connect fan coil #1 to the branch controller allowing that office to choose to be in heating or cooling mode, in this case heating.

Then without having to install another outdoor unit we can add fan coil #2 to the branch controller and that office can be in cooling mode. The same for fan coil #3, we just pipe the fan coil to the branch controller box and that office can choose any mode of operation, in this case heating.

This can all be done using one outdoor unit with a 3-port branch controller, which is one of the advantages of using a heat recovery system as opposed to a VRF Heat Pump System. The heat Recovery system also makes great use of the heat being rejected. The heat rejected from fan coil #2 can be used to heat the spaces serving fan coil #1 and #3.

Cost of VRF Systems

To determine which system is more expensive an analysis will have to be done. If we have two small identical office buildings as shown here, with the first building using a VRF heat pump system. The heat pump system would require at least two outdoor units, one for the South exposure and the other for the North exposure.

The Heat Recovery system is perfect for this type of balanced zoning, and will require only one outdoor unit, but will need a Branch Controller box to route heating or cooling to the indoor units. 

VRF Heat Pump versus VRF Heat Recovery (Cost Factors)
VRF Heat Pump versus VRF Heat Recovery (Cost Factors)

The total amount of piping, fittings and insulation cost will need to be determined between the two designs. 

All of the outdoor units and the Branch controller will need electrical power. All of the indoor fan coils will have their own controller, so there is no difference in cost between the two systems here.

The VRF Heat Recovery systems will most likely require the greatest initial investment when compared to VRF Heat Pump or traditional air conditioning systems. The additional cost for the VRF Heat recovery system comes from having more components and a higher level of installation and commissioning cost. 

The initial cost of a VRF system should be analyzed based on life cycle cost which will be impacted by the energy cost and savings factors.

If you are an HVAC contractor or Engineer that tracks the cost of VRF Systems, then the VRF Wizard has a VRF System Cost Spreadsheet for keeping track of these types of projects. To get this spreadsheet click on this link >> VRF System Cost Tracking Spreadsheet.

Mode of Operation

All air conditioning systems including VRF systems are made to move heat from one location to another depending on the mode of operation. Heat is either brought into the building or rejected out of the building.

Using a VRF Heat Pump in cooling mode, heat is absorbed into the refrigerant from the warm indoor air blowing over the coil. The heat is then circulated by the compressor to the outdoor unit where the heat is rejected through the outdoor coil into the outdoor air. For a complete understanding of the refrigeration cycle see our video on “Refrigerant Cycle 101”.

The heat pump has a reversing valve which changes the direction of flow to each of the two coils. In Heating mode, the indoor coil now becomes the outdoor coil. So during the cold winter, the outdoor coil acts as the evaporator and absorbs heat from the cold outdoor air. You’re properly wondering how there is any heat in the cold winter air.

Well, this is the magic of refrigerants, as R410A is commonly used in VRF systems, and this refrigerant boils at -55.3F (-48.5C). That means this refrigerant circulating in the VRF System can still absorb heat from the cold outdoors and send it to the space to be heated. See our video on “How Heat Pumps Work” for a better explanation.

So it’s easy to remember, one coil absorbs heat (takes it in) and the other rejects heat (throws it out) all with the magic of refrigerants.

A much better and more efficient use of the heat being removed is to use it for some purpose, such as for a room needing heat while another zone is in cooling mode, this is what a Heat Recovery system is good at. 

With a VRF Heat Recovery System, the Branch Controller will either send the heat absorbing or heat rejecting refrigerant to any space depending on whether the space wants heating or cooling, based on the demand of the controller.

So, if heat is absorbed into the refrigerant from a space needing cooling, it can be rejected by the refrigerant into a space needing heating. This is the basic principle of a VRF Heat Recovery System. We’ll cover these systems in more depth in other videos.

When should you use a VRF Heat Pump versus a VRF Heat Recovery System?

The decision will be based on several factors, one of which is what do we want to do with the heat that is recovered from a space. Do we want to throw it away, like we do in a traditional air conditioner, or do we want to use it somewhere else? 

The main difference between the VRF Heat Recovery and Heat Pump system is that the VRF Heat Recovery uses the heat which allows for simultaneous heating and cooling. 

VRF System Comparison
VRF System Comparison

The VRF Heat pump system allows for only one mode of operation at a time. This means that you have the choice to have all the zones in heating mode or all in cooling mode.  If you have one space calling for heating and another for cooling, the one with the controller will determine the mode of operation. The heat pump uses a reversing valve to change the direction of the refrigerant flow. See our video on “How Heat Pumps Work”. 

Therefore, VRF Heat Pump systems need to be designed with zones having similar load profiles, such as all spaces have exterior South facing offices. 

The VRF Heat Recovery System uses a Branch Controller to send cooling or heating to any of the zones connected to the system. The branch controller acts like a Flight Controller, directing traffic. This allows for the heat rejected from one space to heat another space on a different zone.

Heat is removed from a space requiring cooling and rejected through the indoor coil into another space requiring heating. This is the efficient use of energy as its utilized instead of with traditional air conditioners where this heat gets rejected to the outdoors.

In an all-air system, heat is moved from one coil to another. This means in a heat pump system there is an indoor and outdoor coil, so heat is either entering the outdoor coil or exiting the coil. With a VRF Heat Recovery system this same heat can be entering or exiting any of the indoor coils, allowing for either heating or cooling at the same time.

The designer will need to review the owners’ requirements, how the building is oriented, the need for simultaneous heating and cooling, zoning layout, ventilation requirements, and accessibility for routing of piping and or ductwork including available space for new equipment.

Simultaneous Heating and Cooling with VRF Heat Recovery System

The decision on which system to use comes down to whether the zone can take advantage of simultaneous heating and cooling. This requires that the cooling and heating loads are balanced. Another consideration is the cost, as the initial cost of the VRF Heat Recovery System is higher.

Its possible to provide VRF Heat Pumps for each zone, but if you have a lot of zones that are balanced then it probably makes more sense to use a VRF Heat Recovery system, as this can save energy and reduce the number of outdoor units required for the total tonnage.

Depending on the configuration of the spaces and the orientation of the building, the use of a VRF heat pump system can reduce cost and installation and commissioning time by simplifying the install and commissioning process.

Here is a simple example of the differences with an analysis of a building that has the same north and south exposure areas. There are two options. 

First, we can install a VRF Heat Pump Systems, one for the North Zone and another for the South Zone. That way when the North calls for heating all the North zones can be in heating mode, while at the same time the South Zones is in cooling mode. Two separate systems operating in two different modes. This requires a minimum of two outdoor units and at least two indoor units.

VRF Heat Pump System

Outdoor Units required = 2

Indoor Units required = 2 minimum

With the VRF Heat Recovery System this can be accomplished with just one Outdoor Unit and two indoor fan coils or more depending on the zone size.

VRF Heat Recovery System

Outdoor Units required = 1

Indoor Units required = 2 minimum

Controller Box = 1 minimum

As our example shows, we’ll need two outdoor units when designing for a Heat Pump system, and only one for a Heat Recovery System.

The engineer needs to determine what the owners project requirements (OPR’s) are and how to best accomplish those. How the building is zoned, the type of spaces and the operating schedule of the various spaces will need to be considered. Do the spaces share the same orientation to the sun?

You can see in the image below that with a Heat Pump system you’ll have all zones in Heating or Cooling, there is no simultaneous heating and cooling. You can switch to all cooling or all heating.

If you have a long southern exposure in the northern hemisphere, during the summer the South facing spaces may require cooling, while the North exposure may want heating during various hours of the day.

This could be accomplished with two Heat Pump systems or just one Heat Recovery System depending on the size of the zone. Interior zones are usually in cooling mode to satisfy the internal heat gains from people, lights and plug loads, since they have no exterior exposure.

A Heat Recovery System could be a good option if the load profile is balanced allowing for simultaneous heating and cooling. This allows for the heat that is recovered from the space being cooled to be used in spaces requiring heating, hence the terminology Heat Recovery. For locations that have very cold winters, the engineer must ensure that the VRF system can meet the design load at these extreme temperatures, otherwise supplemental heating maybe required.

Heat Recovery Branch Selector Control Boxes

The VRF Heat Recovery system will require an additional component when compared to the VRF heat pump system. With a heat recovery system there is the need to install a box controller between the outdoor and indoor units. This box controller can handle dozens of indoor units, not just one.

The branch controller box acts like a traffic controller, sending either hot gas to zones requiring heating, or sending cold low pressure liquid refrigerant to those zones needing cooling. You will find that the different VRF manufacturers have different names for this controller box.

These boxes require an electrical connection which adds to the cost of these systems, and depending on which manufacture you use, there might also be the need for a condensate drain.

VRF Indoor Unit Sizing and Style

The heating and cooling load will determine the size of the indoor units. For locations where the winters are extreme the selection may be based on the heating load to make sure that the VRF system can handle the extreme winters. The engineer will size the unit based on the meeting the maximum heating or cooling capacity.

Indoor units come in various styles and configurations. They can be ducted or un-ducted. There are un-ducted wall and ceiling mounted units and concealed ducted indoor units. You can serve more than one space when using the ducted units. With the concealed ducted units there is no visible component expect for the air distribution grille requires for the supply and return air paths from the space. With a ceiling or wall mounted unit, the VRF equipment is visible to the occupants and must be taken into consideration for aesthetic reasons.

Space Allocation Requirements

The use of a VRF system is less invasive for renovation projects when compared to an all-air system. The routing of small copper ACR piping is a lot easier than routing larger air ducts to each space when working in an existing building. The capacity of piping to carry the cooling or heating load is much greater than that of air ducts on an area basis. Looking at the chart we can see that the same carrying capacity in tonnage between refrigerant piping and air ducts requires a much smaller piping than air ducts.

Comparison of Air Duct vs ACR Piping (20--Tons of Capacity)
Comparison of Air Duct vs ACR Piping (20–Tons of Capacity)

If a Heat Recovery system is being installed, then additional space will be needed for the branch controller box.

VRF Electrical Requirements

VRF Heat Recovery systems require three electrical connections, as an additional electrical connection is required at the branch controller box. Traditional split system air conditioners and heat pumps typically have two connections, one at the outdoor unit and another at the indoor unit. If using a rooftop packaged unit, then only one electrical connection is required. On small split systems the outdoor unit may come with cabling that powers the indoor unit.

Packaged AC Unit – 1 Electrical Connection

VRF Heat Pump – 2 Electrical Connections

VRF Heat Recovery – 3 Electrical Connections

Limitations on VRF Piping

The use of a VRF system requires that attention be paid to the distances between all the components. This is to ensure that the system operates correctly. The traditional split system air conditioner also has limitation on the distance piping can be ran, and if that distance is exceeded there could be a drop in capacity and or failure of the system to return any oil required by the compressor.

If we look at one of the VRF manufacturers product data sheets, we can see that there are piping limitations for various distances between components.

The engineer has the option of choosing which systems to use for the different areas of a building. Some areas or floors of the building maybe suitable for a VRF Heat Recovery System, a Heat Pump System, Traditional Air Conditioners, or a central plant of some type. The engineer can mix and match these systems by using more than one type of system within the building.

Energy Efficiency of VRF Systems

The use of VRF systems can save on energy compared to the traditional air conditioners. This is one of the benefits when using VRF. There is one or more compressor in an outdoor unit of a VRF system. These compressors can be digital scrolls or similar that can save energy by matching the compressor output to the cooling or heating demand for the system. 

The compressor ramps up and down to match capacity, saving energy by only pumping the volume of refrigerant required to meet the current load. The fans on some of there outdoor units can speed up or slow down to match capacity also. The traditional air conditioner just cycles on and off to meet demand, which is not as efficient as the modulation of these inverter and/or digital scroll compressors.

ASHRAE 62.1 Ventilation Requirements

All occupied spaces require ventilation, that is fresh outside air for the occupants of the building. This is usually done in accordance with ASHRAE standard 62.1, which defines the quantity of ventilation air required based on occupancy levels and area of the space. ASHRAE stands for the American Society of Heating, Refrigeration and Air Conditioning Engineers. They work on establishing standards for the industry and have branches all around the world.

There are several methods for providing outdoor or ventilation air to the occupied space when using a VRF system. Bringing in outside air is energy intensive, especially in hot or humid climates where levels of moisture are high. VRF indoor coils are not efficient at removing a lot of latent loads, as they have high sensible heat ratios.

Sensible heat ratios define the amount of sensible heat to total heat that the unit can provide. The difference between the total and the sensible is the latent load. This means that the higher the sensible heat ratio, the lower its ability to remove latent or moisture from the air.

This means that areas that have high moisture levels will need a way to precondition the air before its delivered to a VRF system. This can be done with a Dedicated Outside Air System (DOAS) unit. The DOAS unit will remove moisture from the outside air and deliver this condition air either directly or indirectly to the VRF indoor unit. See our video on “How Dedicated Outside Air Systems Work”.

Schedule of Occupancy

The time when spaces are occupied is an important factor when engineering a system. Zones with similar occupancy schedules can be combined on the same system which allows for optimal tonnage selection. Spaces with varying occupancy schedules, those spaces that might be used intermittently and not on a regular schedule will require additional analysis and likely a separate system for optimal energy usage.

For instance, small IT closets or areas that require 24 hours a day, 7 days a week operation would not make sense on a larger house system. You don’t want to run a large system off hours to feed a small load. These loads are best off with their own system.

Other spaces like schools and offices usually have a fixed schedule that can be relied upon for accurate programming of a schedule. Spaces that have varying occupancies levels like meeting rooms, conference rooms, and assembly halls can benefit from a dedicated system to meet the unpredictable schedule. Any spaces that produce high levels of moisture will need to be evaluated for their latent load component as the VRF fan coil unit has a high sensible heat ratio (SHR) and doesn’t handle lots of latent load.

When designing a VRF system or any system, occupancy schedule is an important consideration. VRF Heat Recovery systems require similar occupancy schedules to be energy efficient. Its important to balance the heat rejection from the cooling needs with the heating requirements of the system. This allows for the use of the rejected heat to be used for heating simultaneously while cooling is demanded. 

Summary

The use of a VRF system can save energy but comes with a higher initial cost. A payback analysis will need to be run to determine the payback period based on the energy savings and the customer required ROI. The use of the VRF Heat Recovery system allows for greater savings if the system has a good balance between the heat rejected for cooling zones being utilized to those zones needing heating. A balanced heat recovery system allows for simultaneous heating and cooling, while heat pumps only allow one mode of operation for the complete coverage area. VRF systems are a good option for renovations because they are less invasive to the existing structure.

The engineer might consider the following when deciding which VRF system to use.

  1. Does the zone layout benefit from simultaneous heating and cooling by allowing the heat rejected from one space to be used by another?
  2. Is initial cost the determining factor, as VRF Heat Recovery often has the highest initial investment?
  3. Does the area have high moisture or relative humidity? This will require the use of additional equipment such as a DOAS unit to remove the moisture or latent heat.
  4. How will code required ventilation air be provided to the space?
  5. Are the occupancy schedules of the various spaces similar?
  6. Is there space for the branch Selector Box if using a Heat Recovery System?
  7. Where can the outdoor units be located in relationship to the indoor units?
  8. Is refrigerant monitoring required and do the spaces meet the minimum volume for the ASHRAE 15 requirements?
VRF Heat Recovery vs VRF Heat Pump

How Fan Walls or Fan Arrays Work

0
Learn how Fan Walls or Fan Arrays work, how they are built and wired. Learn how to retrofit an existing air handler

How Fan Walls or Fan Arrays Work. Fan walls are fans configured in stackable or wall mounted modules that can be designed in various arrays to form a larger fan system. They have a host of benefits over traditional fans used in the HVAC industry that we’ll cover in this article. One of those benefits is their simple modular design which replaces the single larger, heavier fans of earlier designs.

If you prefer you can watch the Video of this presentation by scrolling to the bottom or clicking on the following link “How Fan Walls or Fan Arrays Work“.

Retrofit Air Handler for New fan Wall (Remove Old Fans)
Retrofit Air Handler for New fan Wall (Remove Old Fans)

We’ll first show you how an air handler gets renovated with a new Fan Wall System. Here we show a large air handler with one large utility style fan inside. The system will be shutdown and the fan will be removed. You can see here that the fan was removed from this air handler so that a new bulkhead sheet metal wall could be installed to hold the new fan arrays. So that is what we’ll do here. 

We’ll install the bulkhead walls, including vertical and horizontal panels, which leaves us an opening in the bulkhead for the fans. Each panel will come from the factory with a sticker that identifies which air handler it applies to, and where the panel is to be installed according to the manufacturer provided assembly drawing. 

Next the fans will be installed. Here we show what the fan might look like from the side view. Each manufacturer provides similar looking fans with various modifications. Next, we put another fan, until all five are installed. 

A quick connect box is installed inside the air handler. The quick connect box connects directly to the bulkhead wall and provides quick connection points for all the cabling coming from the fans. Each fan has power and communication wiring connected to the quick connect box. This part of the installation can be done without an electrician as the connections are just plugged into receptors at each end.

A control box will be installed on the outside of the air handler. Then the electrician will run line voltage power to the control box, and then over to the quick connection box located inside the air handler.

Fan Wall Array with Quick Connect Box and High Pressure Safety Switch
Fan Wall Array with Quick Connect Box and High Pressure Safety Switch

There are cable ties for quickly securing all cabling tight to the wall. The location of these ties is clearly shown on the drawings.

Then we install safety devices such as smoke detectors or pressure sensors. A high pressure limit switch prevents excessive pressure from occurring in the main duct. This will be wired to the control box, and if high pressure is sensed in the duct a signal is sent to the control box to shut-off the fans This could also be any fire/life safety device such as smoke detectors. If smoke is detected, a signal is sent to the fans control box and the fans are shut-off, this prevents smoke from being blown throughout the building.

If one fan breaks down and needs to be removed, just replace it with a blank-off panel until the new fan arrives. This allows the system to remain running using the remainder of the fans. If this were a single utility or vane axial fan that burned-out, the whole system would be down until a new fan was installed. This allows for redundancy with multiple small fans compared to one large fan. 

Built-up Fan Wall or Fan Arrays

Fan walls or fan arrays can be used for built-up systems also. They can be provided in stackable cubes in various configurations. We can have a 1 x 2 array, that is one fan high by two fans wide, or a 1 x 3, or a 2 by 3 fan array. As you can see you can increase the required airflow by increasing the number of fans in the system. All you need is the space for the fans.

Fan Wall Fan Array 2 high x 3 Wide (2x3 Fan Array)
Fan Wall Fan Array 2 high x 3 Wide (2×3 Fan Array)

They can easily fit through doorways and up elevators, making retrofit projects easier. The smaller fan cubes are lighter and easier to handle than single larger fans. This eliminates the need for large cranes or rental equipment.

In retrofit applications, large single utility fans or vane axial fans are often cut apart to allow for easy removal down an elevator, along with any sound traps. Fan Walls run quieter and generate less vibration than the typical fan and are used without sound traps, which also reduces any pressure drop caused by a sound trap.

Fan Wall using Stackable Fan Cubes
Fan Wall using Stackable Fan Cubes

A 3 x 3 fan array gives us 9 fans. They’re stacked on top of each other and fasten together. Here we have a 3 x 4 fan array shown above. There will need to be a wall that isolates the discharge and suction sides of the fan. This can be done by installing some form of framing on both sides of the fan array and then closing any openings with sheet metal blank-off panels. 

Now we have 15 fans running in this built-up system providing air to our building. With all these fans, if anyone was to fail, the system has built-in redundancy as there are 14 other fans still running.

3 x 5 Fan Array = 15 fans - 1 Failed = 14 Fans Still Running (Redundancy)
3 x 5 Fan Array = 15 fans – 1 Failed = 14 Fans Still Running (Redundancy)

The fan array also provides better laminar flow as the air is spread out across the coil face area and isn’t concentrated in one area as you might get with a single utility or vane axial fan. Retrofits can be done over a weekend when the building is unoccupied, reducing or eliminating any down time for the AC system.

Control Systems for Fan Arrays

Here are a few ways in which these fans can be controlled with the use of a DDC programmable controller that uses inputs and outputs with the option of remote control using a Building Management System. Remember from our other basic controls videos that controllers have internally programmable logic, like mini-computers that house software specifically for the application of the equipment. See our other control videos on “Basic HVAC Controls” or “6 Steps for Designing HVAC DDC Controls”, 

They can be controlled by a supply duct static pressure sensor, which attempts to maintain a static pressure set point, or supply CFM control.  They can use return airflow control using building pressurization setpoints, or return air fans can be controlled as a percentage of the supply CFM. There are various other methods of control using the controller.

These controllers can be programmed to only run the system during building operational hours by the use of schedules. The controllers can track alarms, scale the CFM of individual fan cells, enable or disable fan cells. 

Air Handler with Return Air and Supply Air Fan Walls
Air Handler with Return Air and Supply Air Fan Walls

What are some of the Benefits to using a Fan Wall Array?

Some of the benefits to using a Fanwall array is their lighter weight and ease of installation, reduced noise and vibration levels compared to other fan types, reduced building space required, the reduction in downtime due to motor failure because of the use of multiple smaller fans in lieu of a single larger fan installation. 

  • Easier Installation – Smaller Fan Modules are lighter and easier to handle than one large fan. Easier to move and rig the fan array’s smaller modules which can fit through doorways, hallways, stairways or elevators.
  • Reduced Noise & Vibration
  • Redundancy – Multiple Smaller Fans prevent full shutdown in case of motor failure in lieu of the use of one large fan motor.
  • Saves on Real Estate/Building space – Fan arrays usually require less space than a single large fan which often has a sound attenuator that can be removed.
  • Reduced static pressure with the removal of any previously installed sound attenuators. 
  • Usually less costly to install while improving operational efficiency and saving energy & money
  • Eliminates the need for crane rigs or expensive rental equipment or removing walls for equipment access.
  • Reduced cost for maintenance and service
  • Better laminar flow through the coils.
  • Retrofits can be done over a weekend when the building is unoccupied, reducing or eliminating any down time for the AC system.
  • Replaces old technology belt-driven forward curved fans or axial fans. Forward curved fans are less efficient than a backward curved fan found on fan Arrays.
  • No dust or dirt generated by the motors belts deterioration. Important for spaces requiring clean air.
  • EC permanent magnet motor
  • Direct drive motor
  • High efficiency control system
  • High efficiency plug fan
  • Smaller fans and motors running at peak efficiencies

Fan Wall arrays can be used to retrofit an existing built-up larger fan system, Air Handler or Packaged DX piece of equipment. When purchased as part of a new AHU or packaged unit all the components will be factory integrated with controllers and motors. This can be small 15 ton air handlers to ones over 2,000 tons that come fully integrated with Fan Wall Array. As part of a retrofit project, you’ll need to demo the existing fan system and install the Fan wall array modules and connect the electrical and control components in the field.

Fan Array Control Optimization

The fanwalls multiple fan array is optimized for efficiency with controls that vary the speed and quantity of fans in operation at any one time to meet the system requirements.

Each Fanwall manufacturer provides various control packages, from the simple speed controller to the more premium control packages that monitor static pressure and CFM. There may be an option for a fireman’s override, fan RPM, energy usage, individual fan alarm and integration into a BMS system via BACnet.

Variable Frequency Drives

You can add a VFD for each fan or combination of fans to provide for dedicated speed control and a means for on/off fan operation. Various Fan Wall Array manufacturers handle this differently, including one manufacture that includes pre-wired VFD’s, not need for electrician to wire individual fans as they have a simple plug to a local panel

Advantages

Depending on the choice of Fanwall manufactures there are some additional materials and labor required beyond what you purchase from the manufacturer. If your fan wall comes with VFD’s in lieu of ECM motors for speed control, then you’ll need to mount them and wire them to the motors, programming VFD’s and providing electrical to each motor. Fan wall manufactures like Q-PAC avoid most of these issues because they use ECM motors and provide fan power plugs that connect easily to their quick connect panels.

ECM vs VFD Speed Control

Some Fan walls use VFD’s for speed control either with a dedicated VFD per motor or with one VFD handling multiple fan motors.

Some field installed items when using Fanwalls

In addition to the Fans themselves, the following items if provided by the Fanwall manufacture will most likely have to be field installed; VFD’s, BDD’s, Bulkhead walls, Control Panels, Electrical Conduit & Wire, Structural Supports, duct transition (tying into exist systems)

Physical Size

A single fan array can be a 26” x 26” square module approximately 18” deep and weigh 120 pounds. There are fan wall versions that can be completely broken down to get through an existing 19” wide air handler access panel, and then rebuilt inside the unit. With only a cordless drill, wrench, caulk gun and tape measure. According to Nortek it takes approximately 30 minutes to reassemble a single fan cell, and two to three people to move the assembled cells into place.

The cells arrive at the jobsite tagged by the manufacturer as to where they’re to be installed within the air handler. Each cell is bolted to the adjacent cell, while the bottom cells are bolted to the floor. Once all the cells are installed, sheet metal blanking plates are used to cover any top and side openings left over. An electrical chase is provided along the length of the array to protect the power wiring that connects each cell to the electrical power.

Sound Attenuation

Compared to the utility fan or vane axial fan that the plenum fans often replace, the Fan Wall Array is much quieter. Any existing sound traps are removed as the fans are quieter and the cubes that house the fans are provided with acoustic insulation. With multiple smaller direct drive motors the noise levels are less than those of a single large utility style fan or vane axial fan.

Engineering and Supplier Provided Items

If this is a design/build retrofit project for a built-up system, then you’ll need to provide the jurisdictional authority with a set of MEP and Structural drawings showing the new design. This might include structurally engineered drawings showing how the fan array is supported to the structure when using a headwall assembly as opposed to a stackable fan array.

If you are using the Q-PAC fan array system to replace fans in an Air Handler, then you should receive a fully engineered and sized system that fits within the existing air handler. The Q-PAC supplier should provide the following on an Air Handler retrofit:

  • Fully Engineered and sized fan array to meet specified CFM and ESP with ECM motors
  • Factory supplied/field installed modular fan bulkhead wall assembly with precut fan inlets
  • Plug and Play wiring to allow quick connect harness to simply plug into connect panel
  • CFM and Static Pressure measurement plastic tubing
  • Optional – Blank off panels incase a motor goes down.
  • Possibly Factory Supervised Startup. 
  • 5-Year Parts and Labor Warranty. (Confirm with supplier)

Energy Efficiency

The motors used in a Fan Wall Array have individual on/off control and variable speed control, allowing them to maintain operating efficiently along the demand curve of the system. With the variety of fan sizes and quantity of fans available for a fan wall array making it easier to optimize selection to match the best performance requirements.

Fan Walls & Fan Arrays

How to Read Wiring Diagrams in HVAC Systems

0
How to Read HVAC Schematic and Ladder Wiring Diagrams

How to Read Wiring Diagrams in HVAC Systems. There are various types of wiring diagrams used in the HVACR Industry. We’ll explain how to read a schematic wiring diagram and what the various symbols represent and how they function. 

If you prefer to watch the Video version of this presentation you can scroll to the bottom or click on this link “How to Read HVAC Electrical Wiring Diagrams”.

Wiring diagrams are used for the installation of the HVAC equipment, trouble shooting, or locating an electrical device in the control panel or within the unit. There are differences between the type of diagrams based on what they’re used for. 

Schematic Wiring Diagram often called a Ladder Diagram and a Pictorial Diagram
Schematic Wiring Diagram often called a Ladder Diagram and a Pictorial Diagram

The installation diagram will show those connection points most important for connecting the electrical power to the HVAC equipment, while the internal wiring diagrams are meant for troubleshooting by technicians. There is a pictorial diagram that gives a much more cluttered look at the electrical components and wiring as its intended to give you the proximity of the component within the unit.

HVAC Wiring Diagram and Legend
HVAC Wiring Diagram and Legend

We’ll jump right into showing you a schematic diagram for a simple air conditioning unit.

We’ll make a ladder diagram using a simple air conditioner as our example. First we have the main electrical supply lines L1 and L2 providing 208/230 volt, single phase power. Then we’ll need a transformer to provide 24 volt low voltage power for our thermostat, switches and relays. Next we add a thermostat to control the air conditioner, and we connect the power from the low voltage side of the transformer to the “R” terminal of the thermostat.

We’ll need to add an indoor fan motor connection to the line voltage side of the diagram and provide contacts for turning on and off the fan. Next we add the refrigerant compressor to the line voltage side and include contacts and a run capacitor.

To complete our refrigerant circuit we need to add an outdoor condenser fan motor on the line voltage side of the diagram. This provides us with the three largest energy consuming devices in our air conditioner, the compressor, condenser fan and indoor fan motors.

Wiring Diagram showing Electrical Relay Coil on low Voltage side Controlling contacts on the line voltage side.
Wiring Diagram showing Electrical Relay Coil on low Voltage side Controlling contacts on the line voltage side.

Now we need to add some way to control these three motors, which we’ll do from the low voltage side and the use of the thermostat. First we’ll add a compressor relay on the low voltage side of the wiring diagram. This relay will communicate with the compressors contactors on the line voltage side of the wiring diagram as required to start and stop the compressor. 

Also included are some safety devices to protect the compressor from high and low pressure conditions. There is a High Pressure Switch that will shut off the compressor if the pressure in the refrigerant system gets too high. Likewise there is a low pressure switch that will shut off the compressor if the pressure in the refrigerant system gets too low. These safety devices do this by cutting off the low voltage power to the relay coil, which in turn opens the contacts on the line voltage wiring feeding the compressor and outdoor fan. We need to do the same thing for the indoor fan, so we’ll add a relay coil that will open and close a set of contacts on the line voltage side that feeds the indoor fan motor.

Looking at the thermostat we can see that if we move the fan switch to “Auto” then the thermostat will cycle on and off the compressor and indoor fan motor. If we put the fan switch to “On” then low voltage power is always provided to the indoor fan relay, which means that the fan will run all the time, even when the compressor is off.

Let’s look at how the symbols on the diagram relate to actual physical, real world items. This is what an electrical relay might look like without it’s protective cover. We have two relays in our diagram, the Compressor and Indoor Fan Relays. The relay has two main parts, the coil, which is located on the low voltage side of the diagram, and the contacts, which are located on the line voltage side.

When the thermostat is on, low voltage power will be running through its wires energizing the coils of the relays for the indoor fan and compressor. The relay coil will cause the contacts to close which allows line voltage power to energize the compressor, condenser fan and indoor fan motors. When the thermostat is off the coil is de-energized and the contacts open, turning off the compressor and fans. Again, if we energize the coil the contacts close to start the compressor and fans.

We have the pictorial wiring diagram and the schematic wiring diagram. The schematic wiring diagram is also known as a ladder diagram. This is due to its arrangement of vertical lines on each side of horizontal lines which are comprised of electrical components. 

This is a pictorial representation of what the electrical components look like when looking directly at the internal control board. This lets you see where the parts are located, but it’s not as useful for troubleshooting as the schematic ladder wiring diagram we just looked at. The relays are shown as blocks just as the transformers are. This allows us to easily find them within the HVAC equipment, but doesn’t give us a good way of troubleshooting a problem.

Schematic Diagram

The service technician needs to be able to read the wiring diagrams in order to troubleshoot problems. The quickest and less cluttered diagram is the schematic diagram, which shows system functionality without the clutter. The schematic diagram is designed in a ladder format, where line voltage L1 and L2 are shown as vertical lines, and all the electrical components shown on horizontal lines. The lines represent electrical wires while the various symbols are used to represent electrical components, from relays and contacts, to transformers, motors and compressors. There should be a legend that identifies what each symbol represents.

Ladder Wiring Diagram / Schematic Wiring Diagram
How to read wiring diagrams. Ladder Wiring Diagram / Schematic Wiring Diagram

There are symbols for the various types of switches including thermostats and pressure limiting devices. There are symbols for Relays and their corresponding contacts that energize or de-energize circuits. The contacts are shown on the diagram as they would be normally without any electrical power being supplied. You can see that all of our example contacts are what is called normally open, meaning with no power they are set to be open. When a contact is open, no electrical power can flow through it. 

Electrical circuits can flow in series which means there is only one path for electricity to flow or they can be parallel circuits which allow multiple paths for the electricity. 

Once the technician has reviewed the schematic wiring diagram and has a suspicion of the part causing the problem, the pictorial diagram can be referenced to see where that part is located in the unit.

By looking at the schematic wiring diagram the technicians can see how the piece of equipment should be operating by following the modes of operation. If the controller calls for cooling or heating, they should be able to see how the schematic diagram components will be activated to bring on and off the system, along with safety devices that protect the equipment. The schematic diagram allows for a quick view of how the system should operate and allows for troubleshooting any problems.

The technician will find the wiring diagrams attached to an access panel, electrical cover or housed within a internal pocket. 

How to Read Wiring Diagrams in HVAC Systems

How Heat Transfer Works

0
How heat transfer work using radiant, conductive and conductance in buildings

How Heat Transfer Works. There are three basic methods by which heat transfers to and from objects. We’ll explain these three methods and how they’re used in the heating and cooling loads for the sizing of air conditioners and how heat is transferred to and from humans. The heat is measured in BTU’s or Joule.

If you prefer to watch the Video of this presentation, then scroll to the bottom or click on this link. How Heat Transfer Works.

According to the second law of thermodynamics, heat moves from a warmer object to a cooler one. This is how heat uses any of the three methods to move from the outdoors to the indoor environment, or to and from our bodies. We’ll explain the three methods of heat transfer using conduction, radiation and convection, and a fourth one for humans called perspiration.

Three Methods of Heat Transfer

No matter whether you’re at home or in the office, the methods of heat transfer are the same. 

How Heat Transfer Works using Radiation, Conductance and Convection
How Heat Transfer Works using Radiation, Conductance and Convection

Conduction

Conduction is the easiest to understand because as a child you were told not to touch the stove or other hot surfaces or you’ll get burned. You’ll feel the heat transfer when you grab the hot metal handle of a pot on the stove, or touch an object that has been sitting in the hot rays of the sun. This is where heat is transferred by one object coming in contact with another, a direct object to object transfer.

Conduction occurs when heat is passed from one molecule to another in a chain reaction through an object. When heat is added to an object, its molecules speed up as does its temperature. These heated molecules bump into the adjacent molecules causes their velocity to increase and to heat up. This change reaction keeps occurring as long as heat is added or as long as there is an imbalance between molecules. This is most notable when heat is applied to a metal object that you come into contact with.

Three Methods of Heat Transfer - Radiant, Conductance and Convection
Three Methods of Heat Transfer – Radiant, Conductance and Convection

Conduction occurs constantly in the home or office when the outdoor temperature surrounding the walls, windows and roof is different than the indoor temperature. The heat will move through the construction materials at a rate defined by the resistance or “R” value of the material, the total square feet, and the temperature difference between outdoors and indoors. Q = A x U x Delta-T. The “U” value is the inverse of the total resistance of the wall or roof assembly.

The higher the “R” value the less the rate of heat transfer. This is how insulation reduces the heat transfer rate, while metals are highly conductive materials and easily move heat through them.

Three common methods of Heat Transfer include Radiation, Conductance and Convection
Three common methods of Heat Transfer include Radiation, Conductance and Convection

Radiation

Radiation occurs when the sun’s rays travel through space and strikes an object. That object absorbs the heat and can pass the heat along using any of the other heat transfer processes. This is one method by which heat gain occurs in buildings as it falls upon the structure and through windows. 

If you have felt the warmth of a concrete or asphalt sidewalk or street after the sun went down or was blocked by clouds, this would be by conductance as the surface you touch is warm or the warm surface transfer its heat to the air that comes in contact with the surface. You could also feel the heat emanating from the surface as convection, as the air is warmed surrounding the surface and rises upward. 

Radiant Heater as used in a Warehouse. The walls, floors and Objects in room that are in the path with absorb radiant heat
Radiant Heater as used in a Warehouse. The walls, floors and Objects in room that are in the path with absorb radiant heat

This is the same method by which infrared radiant heaters work. They radiate heat through the space until they land on an object that absorbs the heat, which could be a concrete floor in a manufacturing facility or someone working. The heat that hits the floor can than move through the concrete floor by conductance while also emanating upward in the air stream by convection. The walls, floors and ceiling can then radiate this heat back out to objects and the people surrounding the space.

Using the stove as our example again, we would feel the heat radiating out from the hot burner without actually having to touch it. Radiation acts like a waveform, emanating from a warm object to another object without effecting the space in-between. The walls, floors and ceiling can then radiate this heat back out to objects and the people surrounding the space.

To block infrared radiation from coming through windows there are now low-e coatings that can be installed that blocks infrared radiation.

Convection

Convection is the process of heat being dissipated by air motion. As hot air rises off the surfaces of walls it causes air motion that has an effect on human comfort. Heat is transferred from one area to another by the movement or flow of air, which is basically the movement of molecules. Since hot air naturally rises it will cause any heat in the space to be carried by air streams upward.

Air Conditioners and Heat Pumps

The heat that finds its way into your home or office is absorbed by the refrigeration system in your air conditioner or chilled water in some commercial buildings. The warm air is circulated over a refrigerant or chilled water coil where the heat is absorbed into the medium. See our video in the Refrigerant Cycle 101.

The Human Body and the Effects of Heat

The human body can give up heat through the three methods of heat transfer previously discussed, including a fourth one of perspiration. 

Convection occurs when air moves across your body picking up body heat if the air is cooler. This causes the warmer air to rise, inducing cooler air to take its place. The faster the air moves the greater the cooling effect.

Radiation occurs when objects surrounding you are warmer than you are. This causes the object to radiate heat across the space between the object and you. By increasing the heat removal rate with ventilation, the cooler the object will become around you. When you are warmer than the surrounding objects, you’ll radiate heat out from your body.

Perspiration is one of the benefits of the human body as it facilitates the cooling of the body. As moisture evaporates from the skin it cools down the body while removing heat. When air blows across the body while perspiring the effects of evaporation is increased, providing an increased cooling effect. 

How Heat Transfer Works – Radiation, Conduction and Convection