Data Center Refrigerant Economizer

We’ll explain how a free cooling system with a refrigerant economizer works in a data center. Unlike air economizers, which use outside air for cooling, refrigerant economization systems operate differently. These free cooling systems come in a split system or packaged unit version with multiple configurations. 

If you prefer to watch the video version of this presentation, please scroll to the bottom.

Data centers are energy-intensive building types that consume 10 to 50 times the energy per floor space than a typical commercial office building. There are many energy saving strategies for data centers, with one of them being economizers. You have probably heard about air and water-side economizers, but we’ll look at a refrigerant economizer system.

Refrigerant Pump

The heart of the refrigerant economizer is the refrigerant pump. This isn’t the compressor, but a separate pump used to circulate the refrigerant during economizer function. Pumps use less than one-tenth the energy of a compressor, allowing for energy savings. The pump is located below the receiver and condenser.

The pump takes the high-side sub-cooled liquid leaving the condenser and moves it to the expansion valve while maintaining a differential pressure for proper operation. When outside air conditions are unfavorable, the compressors come on and the pumps are bypassed.

Economizer Differences

Refrigerant allows for greater heat absorption capacity than either of air or water. Refrigerant carries as much as two times the heat of water, and 40 times as much as air. This allows for smaller pipes, and the avoidance of large air ducts and contaminated air coming in and out of the building with an air-side economizer. 

Modes of Operation

There are three basic modes of operation with these units. One is that the data center unit runs in full compressor mode without the use of an economizer. The second mode is to be in full refrigerant pump mode under economizer operation, and where the compressors are fully off.

And the last method is to use both the compressor and pump in a mixed mode operation. The mixed mode method requires that there are two circuits. This allows one circuit to be pumping refrigerant in economizer mode, while the other circuit is using a compressor.

Refrigerant Cycle Chart - Normal Cycle vs Refrigerant Economizer Cycle
Refrigerant Cycle Chart – Normal Cycle vs Refrigerant Economizer Cycle

For those that love the engineering aspect, here is a look at what the refrigerant chart says the system is doing in economizer mode. As you can see during the normal refrigerant cycle the compressor raises the pressure significantly. That doesn’t occur during the refrigerant economizer cycle when the compressor is off.

Since there is no compressor to raise the pressure our line flattens out on the vertical pressure line. The compressor is gone, and a pump is added to cycle the refrigerant around the system. See our video on How to Read Refrigerant Charts for a better explanation.

Split System

The first option is the use of a split system where the condenser sits on a stand on the roof. There is a an additional piece of equipment that houses the refrigerant pump. A refrigerant receiver collects liquid coming from the condenser and feeds it to the refrigerant pump. During economizer mode, the pump will circulate the refrigerant while the compressors are off, or during mixed mode both could be operating on separate circuits.

Data Center Refrigerant Economizer - Split System
Data Center Refrigerant Economizer – Split System

There is also the option to have the refrigerant pump housed with the condenser, but the operation is the same.

Refrigerant Economizer using a Refrigerant Pump
Refrigerant Economizer using a Refrigerant Pump

The indoor unit will house the compressors and evaporator coil. The liquid refrigerant will go through the electronic expansion valve before entering the evaporator coil. Warm air from the IT equipment racks will enter the top of the unit before passing over filters, than the through the evaporator coil where the heat gets absorbed. The now cooler air will be sent out the bottom of the unit to the underfloor supply plenum, where it will travel through perforated floor tiles and reenter the IT equipment to repeat the cycle.

There are other styles of the indoor unit where there is no need for a raised floor, and where the return air is located on the bottom front of the unit. The supply air will come off the top.

Packaged Units

Another configuration is the packaged unit, where the condenser, compressor, evaporator and refrigerant pump are all housed in one larger unit. The unit can be installed on the side of a building and the supply and return air ducted into the data center. Some form of isolation between the supply and return is required to avoid short circuiting of the air.

Refrigerant Economizer using a Packaged Unit
Refrigerant Economizer using a Packaged System

There is also a packaged unit version that can sit on the roof of the building and be ducted to the data center space. The same consideration needs to be made to ensure that the supply and return air pathways don’t short circuit before entering the IT equipment.

See our other article about Data Center HVAC Systems, or watch the video about Data Center HVAC Systems

Refrigerant Economizer in a Data Center

Heat Pumps vs Furnaces: Pros and Cons

For smaller heating systems or areas, you have several options, with two of the most common choices being heat pumps and furnaces.  Both systems have their advantages and disadvantages, and understanding the pros and cons of each can help you make an informed decision. In this blog post, we’ll compare heat pumps and furnaces to help you determine which one is the right choice for your heating needs.

If you prefer to watch the Video of this presentation, scroll to the bottom.

Heat Pumps

According to the estimates from the New York State Energy Research and Development Authority, Americans bought more than 4.3 million heat pumps in 2022, compared to roughly 3.9 million natural gas furnaces.

Advantages of Heat Pumps

Split System Heat Pump
Split System Heat Pump

Energy Efficiency

Heat pumps are highly efficient and can provide both heating and cooling. They work by transferring heat from the outside air (or ground) into your home, making them energy-efficient in milder climates. Heat pumps are efficient because they use electricity to transfer heat, rather than create heat by burning a fossil-fuel like natural gas. As the outside air temperature drops, the efficiency will also drop, this is when a high efficiencyfurnace would be a better solution.

Lower Operating Costs 

Because they use electricity to move heat rather than generate it, heat pumps can lead to lower lifetime operating cost, especially in regions with moderate climates. Although gas is usually cheaper than electricity, gas furnaces have a greater lifetime operating cost due to maintenance and repair cost. This is dependent on the cost of electricity and fuel in your area.

Year-Round Comfort 

Heat pumps offer both heating and cooling functions, eliminating the need for a separate air conditioner in the summer. A heat pump uses a reversing valve, which allows for heat to be absorbed outdoors, even when the weather is cold, and sent to the indoors to provide heating.

Environmentally Friendly

Heat pumps produce fewer greenhouse gas emissions compared to furnaces, contributing to a greener environment. There is a move to eliminate the use of fossil-fuel based appliances in pursuit of zero-emissions. New York has recently passed legislation that would ban fossil-fuel appliances in buildings seven stories or less in 2026.  Whether we like it or not, there is a large push to go all electric, and so we should expect more legislation in this area.

Disadvantages of Heat Pump

Upfront Cost

Heat pump installation costs can be higher than that of furnaces, particularly for geothermal heat pump systems. See our video on how geothermal heat pumps work. Additional cost can be attributed to electrical panel and service upgrades for older homes lacking the additional electrical capacity. This could be offset by utility rebates and incentives.

Performance in Extreme Climates

Air-source heat pumps become less efficient in extremely cold weather, requiring a backup heating source in colder climates. It’s important that the heat pump is sized correctly based on the outdoor design temperature for the region.

Heat pumps lose capacity as the temperature drops. This can cause insufficient heating capacity if the outdoor temperature drops below the outside design temperature. At the point on this chart where the two lines meet is where a secondary source of heat such as electric heater can be initiated on these extreme cold days.

Since these extreme temperatures occur only a small percentage of the time, the energy penalty is small. Most areas can benefit from heat pumps except those in extreme climates below -20 F (-29 C).

Maintenance 

Heat pumps require regular maintenance to ensure optimal performance and lifespan. See our article on Heat Pump Maintenance Tips.

Furnaces

Advantages of Furnaces

Gas Furnace and Split System Air Conditioner
Gas Furnace and Split System Air Conditioner

Effective in Cold Climates

Furnaces, particularly those powered by natural gas or oil, excel in providing consistent and powerful heating, making them suitable for very cold climates. Furnaces are rated by the amount of BTU’s they provide as heat to the space. The heat put out by a natural gas furnace is not affected by the temperature outdoors.

The furnace will always put out the rated BTU’s as long as it’s running properly. For example, if a furnace is rated for 125,000 BTU’s per hour, than it doesn’t matter whether its 65 or 10 degrees out, the furnace still puts out 125,000 BTU’s. This is not the same for heat pumps, who’s capacity is reduced as the weather decreases as previously discussed.

Lower Upfront Costs

Furnaces are often more budget-friendly when it comes to installation costs. As we previously stated heat pumps may require an electrical upgrade.

Quick Warm-Up

Furnaces can heat a home rapidly, providing almost instant comfort.

Longevity

Well-maintained furnaces can have a long lifespan.

Disadvantages of Furnaces

Higher Lifetime Operating Costs

Furnaces tend to have higher lifetime operating costs compared to heat pumps, especially if powered by oil or electric resistance heating. Because of the cost associated with maintenance and repairs, furnaces tend to have higher lifetime cost, although they most often have lower operating cost based on the cost of natural gas in your region. 

Some may have Limited Efficiency 

Furnaces generate heat, which can be less energy-efficient in moderate climates than heat transfer methods used by heat pumps. Newer condensing furnaces can achieve efficiencies above 90% and are more efficient in extreme cold climates.

Environmental Impact

Furnaces that run on oil, coal or natural gas can have a significant environmental impact due to emissions. As previously mentioned, there is a global move to get away from fossil fuels.

Separate Cooling System 

Furnaces don’t provide cooling, so you’ll need a separate air conditioning system if you want both heating and cooling capabilities. There are three main components for a split system gas/electric air conditioner. There is the outdoor condensing unit, the indoor furnace and cooling coil.

In summary, the choice between a heat pump and a furnace depends on your specific needs, climate, budget, and environmental considerations. Heat pumps are generally more energy-efficient and environmentally friendly, while furnaces are known for their effectiveness in extreme cold. By evaluating the pros and cons of each system, you can make an informed decision that best suits your home and lifestyle.

If you need help deciding or have questions about heating options for your home, don’t hesitate to reach out to a professional HVAC technician who can provide expert advice tailored to your situation.

Heat Pumps vs Furnaces

Heat Pump Maintenance Tips

A heat pump is a versatile and energy-efficient HVAC system that provides both heating and cooling for your home. To ensure that your heat pump continues to operate at its best and serves you well throughout the year, regular maintenance is crucial. In this article, we’ll provide you with a comprehensive list of heat pump maintenance tips to help you maintain its efficiency and extend its lifespan. If your looking for a new heat pump, checkout the latest pricing here.

Regular Cleaning

Clean or replace air filters every 1-3 months, as dirty filters can reduce airflow and strain the system.

Keep the outdoor unit free from debris, leaves, and vegetation that could obstruct airflow.

Inspect the Thermostat

Verify that the thermostat is functioning correctly, maintaining accurate temperature settings, and calibrating it if necessary.

Check for Refrigerant Leaks

Inspect the refrigerant lines for leaks. If you notice any refrigerant leakage, contact a professional technician for repairs.

Lubricate Moving Parts

Ensure that all moving parts are well-lubricated to reduce friction and wear. Refer to the manufacturer’s guidelines for specific lubrication points.

Inspect Electrical Connections

Regularly check the electrical connections, ensuring they are tight and secure. Loose connections can lead to system inefficiency and potentially dangerous situations.

Clean the Coils

Clean both the indoor evaporator and outdoor condenser coils annually to remove dirt and debris, which can reduce heat transfer efficiency.

Condensate Drain Maintenance

Clear the condensate drain line to prevent clogs and potential water damage. Ensure proper drainage away from the unit.

Inspect and Clean the Fan Blades

Check the condition of the fan blades and clean them as needed. Bent or dirty fan blades can impair airflow and system efficiency.

Monitor Defrost Cycle:

In cold weather, ensure that the defrost cycle is functioning correctly. A malfunctioning defrost cycle can lead to ice buildup on the outdoor unit.

Calibrate Sensors and Controls

Periodically calibrate sensors and controls to ensure accurate temperature readings and efficient operation.

Check for Unusual Noises:

Listen for unusual noises during operation, such as grinding, squealing, or rattling. These may indicate underlying issues that require attention.

Schedule Professional Maintenance:

Arrange for annual professional maintenance by a certified HVAC technician. They can perform in-depth inspections, tune-ups, and address any potential issues before they become major problems.

Keep Surroundings Clear

Maintain a clear area around the outdoor unit, ensuring that there are no obstructions within two feet. Adequate airflow is crucial for the unit’s efficiency.

Monitor Energy Usage

Keep an eye on your energy bills. A sudden increase in energy consumption could be a sign of a heat pump issue that needs attention.

Plan Seasonal Maintenance

Adjust your maintenance routine seasonally. Focus on cooling-related tasks before the cooling season and heating-related tasks before winter.

By following these heat pump maintenance tips, you can maximize your system’s efficiency, prolong its lifespan, and minimize the risk of unexpected breakdowns. Regular maintenance not only saves you money on energy bills but also ensures that your home remains comfortable year-round.

If you ever encounter issues beyond your DIY capabilities, don’t hesitate to contact a qualified HVAC professional for assistance. Proper care and maintenance will keep your heat pump operating at its best, providing reliable heating and cooling for your home.

Ductless Mini Split vs Central Air Conditioner

Ductless vs. Central Air Conditioning: Which is Right for You?

Choosing the right air conditioning system for your home is a significant decision. Two popular options are ductless mini-split systems and central air conditioning systems. Each has its own set of advantages and disadvantages. In this article, we will compare these two cooling solutions to help you make an informed decision.

If you prefer to watch the video of this presentation than scroll to the bottom.

Ductless Mini-Split Systems

Ductless mini-split systems, also known as mini-splits or split-type air conditioners, are versatile and efficient cooling and heating solutions. Here are some of their key advantages and disadvantages:

Check out the latest cost of Ductless Systems.

Advantages of Ductless Mini-Split Systems:

1. Zoning Flexibility: Mini-splits allow you to create different temperature zones in your home, enabling personalized comfort and energy savings. You can cool or heat specific rooms as needed, as each room will have its own fan coil and controller. See our other video that shows you the differences between single and multi zone mini splits systems.

2. No Ductwork Required: As the name suggests, mini-splits don’t require ducts. This makes them an excellent choice for older homes or spaces without existing ductwork. Installation is typically less invasive and costly. Small copper tubing is easier to route through existing construction than larger air ducts. Refrigerant piping carries more cooling capacity per size than air ducts.

3. Energy Efficiency: Ductless systems are highly energy-efficient because they avoid the energy losses associated with ductwork. Ductwork creates resistance to airflow causes an increase in fan power. Compressor inverter technology allows for precise temperature control and reduces energy consumption by adjusting compressor motor speed.

4. Easy Installation: Professional installation of mini-splits is relatively straightforward and can often be completed in a day or less. See our video on Mini-Split Systems.

5. Quiet Operation: Indoor units of mini-splits are generally quieter than traditional central air systems, ensuring a peaceful indoor environment. There are multiple fan speeds allowing the user to lower the speed for quitter operation.

Disadvantages of Ductless Mini-Split Systems:

1. Upfront Cost: The initial cost of purchasing and installing ductless mini-splits can be higher compared to central air systems. The central system allows economy of scale by having fewer pieces of equipment to install and connect with utilities.

2. Aesthetics: While indoor units are compact and can be mounted on walls, some homeowners find their appearance less aesthetically pleasing compared to the discreet nature of central air vents.

Central Air Conditioning Systems

Central air conditioning systems are the traditional choice for many homes. Here are their key advantages and disadvantages:

Check out the latest cost of Central Air Conditioners.

Advantages of Central Air Conditioning Systems:

1. Whole-House Cooling: Central air systems can efficiently cool an entire house from a single thermostat. They are excellent for larger homes or multi-story buildings.

2. Uniform Temperature: Central air systems provide consistent temperature control throughout the house, eliminating hot or cold spots.

3. Aesthetic Appeal: Central air systems are hidden from view, with vents typically located on the ceiling or floor. This can enhance the overall aesthetics of your living space.

Disadvantages of Central Air Conditioning Systems:

1. Ductwork Required: Central air systems rely on ductwork for air distribution. Installation or retrofitting of ducts can be costly and invasive, especially in older homes.

2. Energy Loss: Ductwork can lead to energy losses due to leaks and poor insulation. This affects overall efficiency.

3. Limited Zoning: While some central systems offer zoning capabilities, they are less flexible compared to mini-splits in terms of creating customized temperature zones. Often central air conditioning systems serve the whole house without consideration for unoccupied spaces.

Conclusion

The choice between ductless mini-split systems and central air conditioning systems ultimately depends on your specific needs and preferences. If you prioritize energy efficiency, zoning flexibility, and don’t mind the upfront cost, ductless mini-splits may be the better choice. However, if you have a larger home and prefer a whole-house cooling approach with a discreet appearance, a central air system might be the way to go.

It’s advisable to consult with an HVAC professional who can assess your home and help you determine which system aligns best with your requirements and budget.

Ductless Mini Split System vs Central Air Conditioning