fbpx
Friday, November 22, 2024
Home Blog Page 9

Chilled Water Pumping Options

In this article we’ll discuss the three different pumping methods used in a central plant for the distribution of chilled water. This includes primary variable flow, primary/secondary with distributed pumping, and primary/secondary variable flow with tertiary pumping. There are many other pumping configurations, but in this article we’ll cover the first three.

If you prefer to watch the video of this presentation, than scroll to the bottom.

Primary Variable Flow Chilled Water Pumping

In a primary-only variable flow chilled water system, the operation is centered around using only primary pumps to circulate chilled water through the entire system. The key feature of this system is the variation of flow rates in response to the cooling load. This provides a more energy-efficient operation. Here’s an overview of how the primary-only variable flow chilled water system pumping arrangement typically works:

Primary only variable chilled water pumping
Primary only variable chilled water pumping

Chillers

Chilled water is generated by one or more chillers in the system. There is a chilled water temperature sensor in the chilled water supply pipe leaving the chiller. The chiller cools the water to the desired chilled water supply temperature before it is sent to the cooling coils. 

The 3-way valve ensures that the chiller receives the minimum flow required by the chiller manufacturer. The 3-way valve bypasses the coil when the demand for cooling is reduced at this coil. This provides the chiller with a minimum amount of flow. There are better ways to do this that we’ll cover in another video.

The chilled water is then distributed to the various cooling loads, such as air handling units (AHUs), fan coil units (FCUs), or other cooling devices in the building. The chilled water is distributed using variable speed pumps.

Primary Chilled Water Pumps

The system relies on one or more primary chilled water pumps to circulate water through the chillers and the entire distribution system. These pumps are typically equipped with variable frequency drives (VFDs). The VFD’s adjust the pump speed and flow rates based on the demand. VFDs on the primary pumps allow for the adjustment of the pump speed to match the varying cooling load. Lower pump speeds during periods of lower demand contribute to energy savings. The demand is determined by a differential pressure sensor installed at a remote location.

Differential Pressure Sensor

The cooling coils have supply air temperature sensors that control the amount of chilled water flowing through the control valves. As demand in the space reduces, the 2-way valves modulate toward the closed position. This causes an increase in pressure within the chilled water system. This increase in pressure is sensed by the differential pressure sensor and is communicated to the VFD. The VFD then slows down the speed of the pump, which reduces the amount of chilled water circulated throughout the system.

Energy Efficiency

The system’s energy efficiency is enhanced by avoiding the need for secondary pumps and the associated energy consumption in a primary-secondary system. The variable flow nature ensures that the system operates at optimal conditions, minimizing energy wastage.

Dynamic Control in Central Plant

The system continuously adapts to changes in the cooling load. This provides dynamic control and improved efficiency over traditional constant flow systems.

This primary-only variable flow chilled water system offers a flexible and energy-efficient solution by adjusting the flow rates in the primary loop based on real-time cooling demand. It’s particularly suitable for applications where load variability is a significant factor.

Primary/Secondary with distributed Pumping

In a primary/secondary variable flow chilled water system with a distributed pumping arrangement, the operation involves two separate loops. There is a primary loop and a secondary loop. This design is often employed in larger and more complex chilled water systems, including more than one building. Here’s an overview of how the system typically operates:

Primary secondary with distributed pumping in Central Plant
Primary secondary with distributed pumping in Central Plant

Primary Chilled Water Pumps in Central Plant

One or more primary pumps circulate chilled water through the chillers and the primary loop. In this design there is a pump dedicated for each chiller. A common leg connects the primary and secondary loops. 

Secondary Chilled Water Pumps

The secondary pumps are outside the central plant and into the buildings, bringing them closer to the cooling coils. The pumps provide the pressure required to bring the water from the common leg through their most remote coil and back to the common leg. These pumps will also operate using VFD’s to match the load of the coils they serve.

Energy Efficiency in Chilled Water Central Plant

The primary/secondary design allows for more precise control over the distribution of chilled water to the loads. This avoids over pressurizing the secondary loop which can occur when the secondary pumps are located within the central plant.

By separating the loops, the system can adapt to changes in the secondary loop without affecting the primary loop. Thereby contributing to overall energy efficiency.

Distributed pumping offers redundancy and flexibility, allowing for continued operation even if one secondary pump is offline for maintenance or repair.

This primary/secondary variable flow chilled water system with a distributed pumping arrangement is a robust solution for larger commercial buildings. This allows for precise control, energy efficiency, and redundancy are critical considerations.

Primary/Secondary Variable Flow with Tertiary Pumping

In a primary/secondary variable flow chilled water system with tertiary pumping, the operation involves three separate loops. There is a primary loop, a secondary loop, and a tertiary loop. This design is employed in large and complex chilled water systems to optimize control and enhance energy efficiency. The primary and secondary pumps can be located in the central plant, thereby allowing the tertiary pumps to be located in the individual buildings where the cooling coils are located. Here’s an overview of how the system typically chilled water pumping operates in this system:

Primary secondary with tertiary pumping. Central Plant
Primary secondary with tertiary pumping. Central Plant

Chilled Water Pumping

Primary chilled water pumps circulate chilled water through the chillers and the primary loop within the central plant.

Secondary chilled water pumps in the central plant circulate chilled water through the secondary loop. The secondary pumps respond to fluctuations in the cooling load requirements within the system using VFD’s.

Tertiary pumps circulate chilled water through the tertiary loop within each building. Tertiary pumping loops are dedicated to specific loads or areas that have unique cooling requirements. You might find this system on the campus of your local University which has a central plant and buildings distributed throughout the campus.

These pumps are provided with VFD’s to regulate the flow based on the specific needs of the tertiary loads within the building.

Variable Frequency Drives (VFDs):

Primary, secondary, and tertiary pumps are typically equipped with variable frequency drives (VFDs) to adjust pump speed and flow rates based on real-time demand. This flexibility ensures that the system operates efficiently under varying conditions.

Energy Efficiency in Central Plant

The primary/secondary/tertiary design allows for precise control over the distribution of chilled water to different types of loads with varying cooling requirements. By separating the loops, the system can adapt to changes in each loop without affecting the others, as a result it contributes to overall energy efficiency.

Dynamic Control and Redundancy

The system provides dynamic control, adapting to changes in the cooling load in real time for each loop. The inclusion of a tertiary loop offers additional redundancy and flexibility for meeting specific cooling needs.

This configuration provides a high level of control and efficiency, making it suitable for large and diverse commercial buildings with complex cooling demands.

Central Plant Chilled Water Pumping Options

Chilled Water Central Plant

In this article we’ll discuss the basics of a chilled water central plant. The main pieces of equipment include a water-cooled chiller, cooling tower, air handler, controls, and the chilled-water and condenser water pumps.

If you prefer to watch the Video of this presentation than scroll to the bottom or click on the following link. Chilled Water Central Plant Basics.

We covered chillers in another video, but we’ll go over the basics here. The chiller contains a refrigeration circuit with the typical components found in a standard air conditioner. There is a compressor that circulates the refrigerant, a condenser, and the evaporator.

Chilled Water Central Plant Diagram
Chilled Water Central Plant Diagram

There are two main loops of water fed from the chiller, one comes from the evaporator and the other from the condenser. The chilled water pumps circulate water from the chiller’s evaporator to the air handler through piping, this comprises the chilled water loop. Then there is the condenser water pump that circulates water from the chiller’s condenser to the cooling tower, this comprises the condenser water loop. 

These makeup the two main water loops found in a water-cooled chiller plant. The chilled water loops purpose is to absorb the heat from the building. The condenser water loops purpose is to reject that heat to the atmosphere.

Chilled Water Loop

The chillers evaporator in the central plant produces chilled water. This CHW which is sent to the air handlers cooling coil and fan coils that serve the building occupants.

Chilled Water Central Plant – Chilled Water Loop

The air handlers and fan coils circulate warm air over their chilled water coils. The coils cools the air sent back to the occupied spaces. The heat from the spaces is sent back to the chillers evaporator in the chilled water return piping. That heat is absorbed into the chillers refrigerant circuit of the evaporator. The compressor then increases its pressure and temperature before sending to the condenser.

Condenser Water Loop

The cooling tower is responsible for rejecting the heat captured from the spaces. The warm refrigerant in the condenser passes the heat onto the condenser water. The warm water leaving the chillers condenser enters the cooling tower.

Central Plant Condenser water loop
Central Plant – Condenser Water Loop

The warm water trickles down over the cooling tower fill. The warm water gives up its heat through evaporation to the air be drawn in by the cooling tower fans. The condenser water pump circulates this cooler water from the bottom basin of the cooling tower back to the chillers condenser to repeat the cycle. 

This is the basic operation of a chilled water central plant. It includes the production of chilled water used to cool the air that serves the occupants of the building. The pumps circulate that water between the chiller and the other components. The air handlers’ job is to pick up the heat from the space by passing the warm air over the cold chilled water coil.

This is the first in our series on Central Plants and their operation. See our other videos on How Air-Cooled and Water-Cooled Chillers work”, and on “How Cooling Towers Work”.

Chilled Water Central Plant

Dual Duct System

In this article we’ll discuss the dual duct system and mixing boxes. Dual duct mixing boxes help regulate the temperature and airflow in buildings by mixing hot and cold air to achieve the desired conditions. 

If you prefer to watch the video of this presentation, than scroll to the bottom.

Here’s how a dual-duct system works.

Depending on the configuration, an air handler can be provided with one or more fans. Next, there will be a heating coil and boiler to provide heat, while a chilled water coil and chiller will provide cooling. There are also other sources available for heating or cooling. 

There will be two main ducts leaving the air handler. One for heating, and the other for cooling, which makes this a dual-duct system. 

Dual Duct System Air Handler with Dual Duct Mixing boxes
Dual Duct System Air Handler with Dual Duct Mixing Terminals

Dual-Duct Mixing Box

Each zone will have its own dual-duct Mixing Box, that can be either constant or variable volume. This allows one zone to be in cooling, while another zone can be in heating. Dual duct boxes are made of galvanized steel and contain two dampers. Each damper has a controller located on the outside of the box. A flow sensor is in the hot and cold inlets of the box allowing for accurate measurement of the air flow. 

Dual Duct System with Hot and Cold Decks
Dual Duct System with Hot and Cold Decks

A room-based temperature sensor or thermostat will continuously monitor the indoor temperature. These sensors provide feedback to the HVAC control system. The control system analyzes the temperature data and determines the required airflow and temperature to maintain the desired conditions.

The dual duct mixing box operates by adjusting dampers within the box. These dampers control the amount of cold and hot air that is mixed before being distributed to different zones within the building.

Mixing Box Operation 

There are various control strategies for dual-duct boxes. One strategy is for there to be no blending of the hot or cold air, which looks like this.

When the thermostat calls for cooling, the damper on the hot air duct closes, and the cold air damper modulates from zero to maximum. This allows cold air to enter the mixing box.

Dual Duct Mixing Box Chart - No Blending of hot and cold duct air
Dual Duct Mixing Box Chart – No Blending of Hot or cold duct air

Conversely, when heating is needed, the damper on the cold air duct closes, and the damper on the hot air duct opens. 

Then there are various blending strategies where a mixture of cold and warm air will mix during certain conditions.

Dual-duct mixing terminal chart - Mixing of hot and cold air streams
Dual-duct mixing terminal chart – Mixing of hot and cold air streams

As the temperature sensor approaches the setpoint in cooling mode, the cold air damper will modulate from maximum to a minimum setpoint. When the temperature continues to drop the hot air damper begins to open creating a mixed air flow. While the temperature continues dropping, the cold air damper completely closes, and the hot air damper modulates to maximum open position.

There are two separate ducts for supplying air. One duct carries cold air, while the other carries hot air. After mixing, the conditioned air is distributed to various areas of the building through separate ductwork. 

Each zone may have its own mixing box, allowing precise control over the temperature and airflow in different parts of the building. Again, this allows any zone to be in either heating or cooling mode.

Dual Duct Air Handler and Dual Duct Mixing Boxes

Whole House Ventilation

In this article we’ll show you four basic methods of whole house ventilation, which in theory explains concepts used in commercial applications. We’ll identify the advantages and disadvantages of each method of ventilation.

If you prefer to watch the video fo this presentation, you can scroll to the bottom.

Exhaust Ventilation Systems

Using exhaust as the primary method of ventilation requires that an exhaust fan creates a negative pressure within the space. The exhaust fan will pull air from the space and exhaust it outdoors. A path for outdoor air to get into the building must be created. The makeup ventilation air can come from leaks in the building construction, such as doors and windows, or from the installation of passive vents.

Whole House Exhaust Ventilation System
Whole House Exhaust Ventilation System

When the exhaust fan is running, it creates a negative pressure causing air to be drawn into the home through the cracks and vents. 

Exhaust systems are simple to install and are relatively less expensive than the other methods. The fan can be installed in the attic if available or on the roof. A single location for the intake of exhaust air can be provided or from multiple locations for a much better design. Air can be exhausted from spaces that generate pollutants, such as the bathrooms or laundry rooms.

The use of passive vents for makeup air prevents the reliance on leakage into the building from the building construction. Passive vents may require larger pressure differences than that produced by the exhaust fan to work correctly. 

With the use of negative pressure as the main method of ventilation, there is the concern that pollutants could be drawn into the space. Pollutants such as dust from attics, radon and mold from crawlspaces, fumes from attached garages, and flue gases from a fireplace or fossil-fuel-fired water heater and furnace. In addition to pollutants, in humid climates, moisture could be drawn into the space, so this method would not be recommended for humid climates. In cold climates the need to mix the outside air with indoor air may be required to avoid cold drafts.

Supply Fan Ventilation Systems

In stead of pulling air out of the building, a supply fan pressurizes the spaces by forcing outside air into the building. This causes the spaces to be under positive pressure, which forces air to leak out of the building through cracks, bathroom exhaust or kitchen range hood exhaust ducts, or through vents if provided. These systems are also one of the easiest and least expensive to install. Again the supply duct can supply one area or preferably several of the most occupied spaces.

Whole-house Supply Ventilation System
Whole-house Supply Ventilation System

By pressurizing the building using a supply fan, unwanted pollutants are minimized from entering due to the pressure relationship between indoors and outdoors. A supply system can also have the outdoor air first enter through a filter to remove dust and pollen.

Supply fan ventilation systems works best in hot or mixed climate regions. In colder climates these systems can cause moisture problems because they pressurize the space. In the cold winter, the warm inside air can be forced into exterior wall and ceiling cavities. If this air is humid, then condensation could condense out causing mold and mildew.

Since there is no conditioning of the air or the removal of moisture through an air conditioning coil before entering the space, these systems could use more energy compared with an energy recovery ventilation system. 

Balanced Ventilation System

The exhaust system creates a negative pressure, while the supply system creates a positive pressure. With a balanced ventilation System, the two cancel each other out to maintained balanced indoor air pressure. If supply air into the space equals the exhaust air volume leaving the space, theoretically you have a balanced system.

Whole-house Balance Ventilation System
Whole-house Balance Ventilation System

With a balanced system you’ll have a supply and exhaust fan serving the space. The strategy is the same when it comes to where the intakes and exhaust locations should be. Supply air should be located in the most occupied spaces, while exhaust should be in areas that generate pollutants.

Having multiple fans and ductwork makes this system more expensive to install and operate than a single fan system. These first three systems do nothing to temper the incoming air or to remove moisture before entering the spaces.

Energy Recovery Ventilation Systems

This whole house ventilation system will cost the most to furnish and install. It also will require more engineering to meet the needs of the spaces. Some energy cost savings comes with the use of a heat-recovery ventilator (HRV) or Energy Recovery Ventilator (ERV). They can reduce the operating cost by transfering heat or energy between the incoming and outgoing air streams. 

Energy or Heat Recovery Ventilation System
Energy or Heat Recovery Ventilation System

In the cold season, heat is transferred from the exhaust air into the cooler ventilation air entering the space. In summer, heat is transferred from the warm ventilation supply air entering the building to the exhaust air leaving. This helps reduce the load on the air conditioner due to the ventilation. 

See our other video on “Heat Recovery Ventilators” for more information.

Whole house ventilation options